background image

036-21528-001-A-0303                                                                                                                                                                                                                               

Unitary Products Group

17

*

KW listed is for 240 volts, use Table 15  for 208 or 230 volts.

** KW listed is for 480 volts, use Table 15  for 460 volts.

TABLE 16: ELECTRICAL DATA (13 SEER HEAT PUMP / ELECTRIC HEAT)

MO

DE

L

BHP

POWER 

SUPPLY

COMPRESSOR

COND

FAN

MOTOR

FLA

SUPPLY

AIR 

BLOWER 

MOTOR 

FLA

ELECTRIC HEAT ACCESSORY

MINIMUM

CIRCUIT

 AMPACITY

MAX.

FUSE/
SIZE,

1

AMPS

MAX

HACR

2

BREAKER

SIZE

RLA

LRA

MODEL NO.

KW

TOTAL 

AMPS

024

208/230-1-60

9.3

57.0

1.1

5.0

2NH04500506

3.8 / 5.0 *

18.1 / 20.8

40.3 / 43.8

45 / 45

45 / 45

2NH04500706

5.6 / 7.5 *

27.1 / 31.3

51.6 / 56.8

60 / 60

60 / 60

2NH04501006

7.5 / 10.0 *

36.1 / 41.7

62.9 / 69.8

70 / 70

70 / 70

030

208/230-1-60

15.0

72.5

1.1

5.0

2NH04500506

3.8 / 5.0 *

18.1 / 20.8

47.4 / 50.9

50 / 60

50 / 60

2NH04500706

5.6 / 7.5 *

27.3 / 31.3

58.7 / 63.9

60 / 70

60 / 70

2NH04501006

7.5 / 10.0 *

36.1 / 41.7

70.0 / 76.9

70 / 80

70 / 80

2NH04501506

11.3 / 15.0 *

54.2 / 62.5

92.6 / 103.0

100 / 110

100 / 110

036

208/230-1-60

17.2

94.0

1.1

7.3

2NH04500506

3.8 / 5.0 *

18.1 / 20.8

52.5 / 55.9

60 / 60

60 / 60

2NH04500706

5.6 / 7.5 *

27.1 / 31.3

63.8 / 69.0

70 / 70

70 / 70

2NH04501006

7.5 / 10.0 *

36.1 / 41.7

75.0 / 82.0

80 / 90

80 / 90

2NH04501506

11.3 / 15.0 *

54.2 / 62.5

97.6 / 108.0

100 / 110

100 / 110

042

208/230-1-60

20.0

104.0

1.1

7.3

2NP04501006

7.5 / 10.0 *

36.1 / 41.7

78.5 / 85.5

80 / 90

80 / 90

2NP04501506

11.3 / 15.0 *

54.2 / 62.5

101.1 / 111.5

110 / 125

110 / 125

048

208/230-1-60

23.4

126.0

1.5

7.3

2NP04501006

7.5 / 10.0 *

36.1 / 41.7

83.2 / 90.1

90 / 100

90 / 100

2NP04501506

11.3 / 15.0 *

54.2 / 62.5

105.8 / 116.2

110 / 125

110 / 125

2NP04502006

15.0 / 20.0 *

72.2 / 83.3

128.3 / 142.2

150 / 150

150 / 150

2NP04502506

18.8 / 25.0 * 90.3 / 104.2

150.9 / 168.3

175 / 175

175 / 175

030

208/230-3-60

10.0

63.0

1.1

5.0

2NH04501025

7.5 / 10.0 *

20.8 / 24.1

44.7 / 48.7

45 / 50

45 / 50

2NH04501525

11.3 / 15.0 *

31.3 / 36.1

57.7 / 63.7

60 / 70

60 / 70

036

208/230-3-60

11.4

78.0

1.1

7.3

2NH04501025

7.5 / 10.0 *

20.8 / 24.1

48.7 / 52.7

50 / 60

50 / 60

2NH04501525

11.3 / 15.0 *

31.3 / 36.1

61.7 / 67.8

70 / 70

70 / 70

042

208/230-3-60

13.9

88.0

1.1

7.3

2NP04501025

7.5 / 10.0 *

20.8 / 24.1

51.8 / 55.8

60 / 60

60 / 60

2NP04501525

11.3 / 15.0 *

31.3 / 36.1

64.9 / 70.9

70 / 80

70 / 80

048

208/230-3-60

13.0

93.0

1.5

7.3

2NP04501025

7.5 / 10.0 *

20.8 / 24.1

51.1 / 55.1

60 / 60

60 / 60

2NP04501525

11.3 / 15.0 *

31.3 / 36.1

64.1 / 70.2

70 / 80

70 / 80

2NP04502025

15.0 / 20.0 *

41.7 / 48.1

77.2 / 85.2

80 / 90

80 / 90

2NP04502525

18.8 / 25.0 *

52.1 / 60.1

90.2 / 100.2

100 / 110

100 / 110

030

460-3-60

5.0

31.0

0.6

5.0

2NH04501046

10.0 **

12.0

27.5

30

30

2NH04501546

15.0 **

18.0

35.4

40

40

036

460-3-60

5.7

40.0

0.6

7.3

2NH04501046

10.0 **

12.0

30.7

35

35

2NH04501546

15.0 **

18.0

38.6

40

40

042

460-3-60

6.4

44.0

0.6

7.3

2NP04501046

10.0 **

12.0

31.6

35

35

2NP04501546

15.0 **

18.0

39.4

40

40

048

460-3-60

6.4

46.5

0.8

7.3

2NP04501046

10.0 **

12.0

31.8

35

35

2NP04501546

15.0 **

18.0

39.6

40

40

2NP04502046

20.0 **

24.1

47.5

50

50

2NP04502546

25.0 **

30.1

55.3

60

60

1.

Dual element, time delay type.

2.

Standard circuit breakers may be used in Canada and on applications over 60 amps where the heaters are separately fused.

Summary of Contents for B1HP024 THRU 048

Page 1: ...aller can fit this unit between the wheel wells of full size pick up truck All models are under 500 pounds All units are completely wired charged with R 22 and tested prior to shipment Unique test sta...

Page 2: ...er water integrity Rounded corners with water drip edges add to the attractive appearance The cabi net panels have a non fibrous insulation that reduces insulation fibers into conditioned area TOP DIS...

Page 3: ...1 leak rate Includes hood and mesh bird screen filter integrated into the hood dry bulb sensor and relief damper Sepa rate field accessories of single enthalpy and dual enthalpy are also available SIN...

Page 4: ...provide single phase models from factory furnished 40 VA trans former capability to 75 VA transformer capability ELECTRIC HEATERS Each heater package provides easy installation of elec tric heat strip...

Page 5: ...RIC HEAT NOMINAL CAPACITY KW 47 F 17 F MBH SEER EER MBH COP MBH COP SINGLE PHASE THREE PHASE 024 24 4 13 0 11 3 7 6 79 21 8 3 40 11 0 2 00 5 0 7 5 10 0 N A 030 30 0 13 0 11 3 7 6 77 28 2 3 40 16 5 2 2...

Page 6: ...R INPUT kW 2 20 2 21 2 17 2 16 2 24 2 24 2 20 2 19 Sensible Capacity MBH 1 Entering Dry Bulb F 86 19 5 21 5 20 5 20 6 20 4 22 3 20 8 20 9 83 17 2 19 2 20 5 20 6 18 5 20 7 20 8 20 9 80 14 9 16 9 19 7 2...

Page 7: ...ER INPUT kW 3 14 3 12 3 04 3 06 3 24 3 22 3 14 3 16 Sensible Capacity MBH 1 Entering Dry Bulb F 86 21 7 26 6 25 0 26 7 23 9 27 9 26 0 27 7 83 18 8 24 1 25 0 26 7 20 6 26 3 26 0 27 7 80 15 9 21 1 25 4...

Page 8: ...PUT kW 3 61 3 52 3 44 3 45 3 70 3 61 3 53 3 54 Sensible Capacity MBH 1 Entering Dry Bulb F 86 23 9 29 4 29 5 30 4 26 2 31 9 30 2 31 1 83 20 9 26 6 29 2 30 0 22 7 28 9 30 2 31 1 80 17 9 23 6 27 8 28 6...

Page 9: ...PUT kW 4 01 3 98 3 89 3 88 4 06 4 03 3 94 3 93 Sensible Capacity MBH 1 Entering Dry Bulb F 86 28 1 34 5 35 2 35 6 29 4 35 8 35 4 35 7 83 24 5 31 6 34 8 35 1 25 6 33 0 35 2 35 5 80 21 0 28 1 33 7 33 8...

Page 10: ...T kW 4 71 4 62 4 52 4 47 4 81 4 71 4 61 4 56 Sensible Capacity MBH 1 Entering Dry Bulb F 86 32 0 40 2 40 1 43 2 33 5 41 8 40 3 43 5 83 28 0 36 5 39 7 41 8 29 2 38 0 40 1 42 7 80 23 9 32 4 39 6 39 3 24...

Page 11: ...e indoor motor heat has been added These power inputs are total power inputs the indoor motor watts have been added TABLE 9 HEATING CAPACITIES 2 1 2 TON BHP030 CFM RETURN AIR F CAP1 KW OUTDOOR AIR TEM...

Page 12: ...the indoor motor heat has been added These power inputs are total power inputs the indoor motor watts have been added TABLE 11 HEATING CAPACITIES 3 1 2 TON BHP042 CFM RETURN AIR F CAP1 KW OUTDOOR AIR...

Page 13: ...KW 2 408 2 634 2 861 3 088 3 315 3 542 3 769 3 996 70 MBH 13 702 16 887 20 812 25 650 31 612 38 961 48 017 59 179 KW 2 792 3 018 3 245 3 472 3 699 3 926 4 153 4 380 80 MBH 12 114 15 299 19 224 24 062...

Page 14: ...CFM 273 324 392 480 541 B1HP042 Electric Heat 1225 CFM 306 341 412 494 577 B1HP042 Cooling TB2 A 1300 CFM 338 395 470 551 640 B1HP042 Cooling TB2 B 1400 CFM 393 466 544 642 734 B1HP042 Heating TB2 A...

Page 15: ...used for all field installed 24 volt wire Only required on units with supplemental electric heat PROGRAMMABLE THERMOSTAT ONLY 24 VOLT TRANSFORMER Label all wires prior to disconnection when servicing...

Page 16: ...15 0 96 75 036 208 230 1 60 187 253 17 2 94 0 1 1 7 3 29 9 45 45 0 96 40 208 230 3 60 187 253 11 4 78 0 1 1 7 3 22 7 30 30 0 96 75 460 3 60 414 504 5 7 40 0 0 6 7 3 15 4 20 20 0 96 75 042 208 230 1 60...

Page 17: ...06 7 5 10 0 36 1 41 7 83 2 90 1 90 100 90 100 2NP04501506 11 3 15 0 54 2 62 5 105 8 116 2 110 125 110 125 2NP04502006 15 0 20 0 72 2 83 3 128 3 142 2 150 150 150 150 2NP04502506 18 8 25 0 90 3 104 2 1...

Page 18: ...102 89 92 042 440 435 120 115 101 104 048 485 480 132 127 111 115 FIGURE 4 UNIT CLEARANCES CLEARANCES NOTE FOR UNITS APPLIED WITH A ROOF CURB THE MINIMUM CLE ARANCE MAY BE REDUCED FROM 1 INCH TO 1 2...

Page 19: ...036 21528 001 A 0303 Unitary Products Group 19 FIGURE 5 UNIT DIMENSIONS...

Page 20: ...036 21528 001 A 0303 20 Unitary Products Group FIGURE 6 TYPICAL APPLICATIONS...

Page 21: ...036 21528 001 A 0303 Unitary Products Group 21 FIGURE 7 ROOF CURB DIMENSIONS...

Page 22: ...036 21528 001 A 0303 22 Unitary Products Group FIGURE 8 TYPICAL WIRING DIAGRAM 208 230 1 60 POWER SUPPLY...

Page 23: ...036 21528 001 A 0303 Unitary Products Group 23 FIGURE 9 TYPICAL WIRING DIAGRAM 230 3 60 POWER SUPPLY...

Page 24: ...036 21528 001 A 0303 24 Unitary Products Group FIGURE 10 TYPICAL WIRING DIAGRAM 460 3 60 POWER SUPPLY...

Page 25: ...l be provided to assure reliable transit of equipment overhead rig ging fork truck access and proper sealing on roof curb applications Base rails shall be removable when required to lower unit height...

Page 26: ...pressures C Unit shall contain a reliable demand defrost control to provide defrost The defrost control shall also have an X terminal to provide a 24 volt signal for room thermostat LED indication of...

Page 27: ...036 21528 001 A 0303 Unitary Products Group 27...

Page 28: ...001 A 0303 Copyright by Unitary Products Group 2003 All rights reserved Supersedes Nothing Unitary 5005 Norman Products York OK Group Drive 73069 This product was manufactured in a plant whose qualit...

Reviews: