background image

036-21528-001-A-0303

4

Unitary Products Group

RECTANGLE TO ROUND ADAPTERS

Kit includes one supply and one return air rectangle to 

round duct adapter. Adapters are preformed and 

designed to fit over current duct openings on the base 

unit. Transition is from 15" square to 14" round.

ROOF CURBS

NRCA approved curbs provide proper fit to base unit 

for rooftop installations. Curbs are designed to be 

assembled through hinge pins in each corner. Kit also 

provides seal strip to assure a water tight seal. Eight 

and 14 inch high roof curbs are available.

MANUAL OUTDOOR DAMPER

Provides 0% thru 50% outdoor air capability (field 

adjustable). Designed for duct mounted side return and 

unit mounted down shot applications. Includes hood 

and screen assembly.

WALL THERMOSTAT

The units are designed to operate with 24-volt elec-

tronic and electro-mechanical thermostats. All units 

can operate with single stage heat / single stage cool 

thermostats - with or without the economizer.

LOW AMBIENT KIT

Kit provides necessary hardware to convert unit to 

operate in cooling cycle down to 0

 F. Standard unit 

operation 45

 F.

TRANSFORMER KIT (SINGLE PHASE ONLY)

Kit provides necessary hardware to provide single 

phase models from factory furnished 40 VA trans-

former capability to 75 VA transformer capability.

ELECTRIC HEATERS

Each heater package provides easy installation of elec-

tric heat strips. Slide in design with plug in harness and 

agency approved. Heaters are available from 5.0 KW 

sizes and are designed for single point and dual con-

nection.

TABLE OF CONTENTS

Description ............................................................................1

Standard Features / Benefits ................................................1

Field-installed Accessories ...................................................3

Unit Cut Away .......................................................................5

Ratings .................................................................................5

Physical Data ........................................................................5

Cooling Capacities - 2 Ton (BHP024)  ..................................6

Cooling Capacities - 2-1/2 Ton (BHP030)  ............................7

Cooling Capacities - 3 Ton (BHP036)  ..................................8

Cooling Capacities - 3-1/2 Ton (BHP042)  ............................9

Cooling Capacities - 4 Ton (BHP048)  ................................10

Heating Capacities - 2 Ton (BHP024)  ................................11

Heating Capacities - 2-1/2  Ton (BHP030)  .........................11

Heating Capacities - 3 Ton (BHP036)  ................................12

Heating Capacities - 3-1/2 Ton (BHP042) ..........................12

Heating Capacities - 4 Ton (BHP048)  ................................13

Side & Bot. Sup. Air Blower Perf. (208/230/460 Volts)  ...... 14

Additional Static Resistance  .............................................. 14

Field Wiring Diagram  ......................................................... 15

Electrical Data (Basic Unit)  ................................................ 16

Electrical Data (13 Seer Heat Pump / Electric Heat)  ......... 17

Application Data ................................................................. 18

Center of Gravity and Weights ........................................... 18

Unit Clearances  ................................................................. 18

Unit Dimensions ................................................................. 19

Typical Applications  ........................................................... 20

Roof Curb Dimensions ....................................................... 21

Typical Wiring Diagram (208/230-1-60 Power Supply)  ...... 22

Typical Wiring Diagram (230-3-60 Power Supply) ............. 23

Typical Wiring Diagram (460-3-60 Power Supply) ............. 24

Mechanical Specifications .................................................. 25

Summary of Contents for B1HP024 THRU 048

Page 1: ...aller can fit this unit between the wheel wells of full size pick up truck All models are under 500 pounds All units are completely wired charged with R 22 and tested prior to shipment Unique test sta...

Page 2: ...er water integrity Rounded corners with water drip edges add to the attractive appearance The cabi net panels have a non fibrous insulation that reduces insulation fibers into conditioned area TOP DIS...

Page 3: ...1 leak rate Includes hood and mesh bird screen filter integrated into the hood dry bulb sensor and relief damper Sepa rate field accessories of single enthalpy and dual enthalpy are also available SIN...

Page 4: ...provide single phase models from factory furnished 40 VA trans former capability to 75 VA transformer capability ELECTRIC HEATERS Each heater package provides easy installation of elec tric heat strip...

Page 5: ...RIC HEAT NOMINAL CAPACITY KW 47 F 17 F MBH SEER EER MBH COP MBH COP SINGLE PHASE THREE PHASE 024 24 4 13 0 11 3 7 6 79 21 8 3 40 11 0 2 00 5 0 7 5 10 0 N A 030 30 0 13 0 11 3 7 6 77 28 2 3 40 16 5 2 2...

Page 6: ...R INPUT kW 2 20 2 21 2 17 2 16 2 24 2 24 2 20 2 19 Sensible Capacity MBH 1 Entering Dry Bulb F 86 19 5 21 5 20 5 20 6 20 4 22 3 20 8 20 9 83 17 2 19 2 20 5 20 6 18 5 20 7 20 8 20 9 80 14 9 16 9 19 7 2...

Page 7: ...ER INPUT kW 3 14 3 12 3 04 3 06 3 24 3 22 3 14 3 16 Sensible Capacity MBH 1 Entering Dry Bulb F 86 21 7 26 6 25 0 26 7 23 9 27 9 26 0 27 7 83 18 8 24 1 25 0 26 7 20 6 26 3 26 0 27 7 80 15 9 21 1 25 4...

Page 8: ...PUT kW 3 61 3 52 3 44 3 45 3 70 3 61 3 53 3 54 Sensible Capacity MBH 1 Entering Dry Bulb F 86 23 9 29 4 29 5 30 4 26 2 31 9 30 2 31 1 83 20 9 26 6 29 2 30 0 22 7 28 9 30 2 31 1 80 17 9 23 6 27 8 28 6...

Page 9: ...PUT kW 4 01 3 98 3 89 3 88 4 06 4 03 3 94 3 93 Sensible Capacity MBH 1 Entering Dry Bulb F 86 28 1 34 5 35 2 35 6 29 4 35 8 35 4 35 7 83 24 5 31 6 34 8 35 1 25 6 33 0 35 2 35 5 80 21 0 28 1 33 7 33 8...

Page 10: ...T kW 4 71 4 62 4 52 4 47 4 81 4 71 4 61 4 56 Sensible Capacity MBH 1 Entering Dry Bulb F 86 32 0 40 2 40 1 43 2 33 5 41 8 40 3 43 5 83 28 0 36 5 39 7 41 8 29 2 38 0 40 1 42 7 80 23 9 32 4 39 6 39 3 24...

Page 11: ...e indoor motor heat has been added These power inputs are total power inputs the indoor motor watts have been added TABLE 9 HEATING CAPACITIES 2 1 2 TON BHP030 CFM RETURN AIR F CAP1 KW OUTDOOR AIR TEM...

Page 12: ...the indoor motor heat has been added These power inputs are total power inputs the indoor motor watts have been added TABLE 11 HEATING CAPACITIES 3 1 2 TON BHP042 CFM RETURN AIR F CAP1 KW OUTDOOR AIR...

Page 13: ...KW 2 408 2 634 2 861 3 088 3 315 3 542 3 769 3 996 70 MBH 13 702 16 887 20 812 25 650 31 612 38 961 48 017 59 179 KW 2 792 3 018 3 245 3 472 3 699 3 926 4 153 4 380 80 MBH 12 114 15 299 19 224 24 062...

Page 14: ...CFM 273 324 392 480 541 B1HP042 Electric Heat 1225 CFM 306 341 412 494 577 B1HP042 Cooling TB2 A 1300 CFM 338 395 470 551 640 B1HP042 Cooling TB2 B 1400 CFM 393 466 544 642 734 B1HP042 Heating TB2 A...

Page 15: ...used for all field installed 24 volt wire Only required on units with supplemental electric heat PROGRAMMABLE THERMOSTAT ONLY 24 VOLT TRANSFORMER Label all wires prior to disconnection when servicing...

Page 16: ...15 0 96 75 036 208 230 1 60 187 253 17 2 94 0 1 1 7 3 29 9 45 45 0 96 40 208 230 3 60 187 253 11 4 78 0 1 1 7 3 22 7 30 30 0 96 75 460 3 60 414 504 5 7 40 0 0 6 7 3 15 4 20 20 0 96 75 042 208 230 1 60...

Page 17: ...06 7 5 10 0 36 1 41 7 83 2 90 1 90 100 90 100 2NP04501506 11 3 15 0 54 2 62 5 105 8 116 2 110 125 110 125 2NP04502006 15 0 20 0 72 2 83 3 128 3 142 2 150 150 150 150 2NP04502506 18 8 25 0 90 3 104 2 1...

Page 18: ...102 89 92 042 440 435 120 115 101 104 048 485 480 132 127 111 115 FIGURE 4 UNIT CLEARANCES CLEARANCES NOTE FOR UNITS APPLIED WITH A ROOF CURB THE MINIMUM CLE ARANCE MAY BE REDUCED FROM 1 INCH TO 1 2...

Page 19: ...036 21528 001 A 0303 Unitary Products Group 19 FIGURE 5 UNIT DIMENSIONS...

Page 20: ...036 21528 001 A 0303 20 Unitary Products Group FIGURE 6 TYPICAL APPLICATIONS...

Page 21: ...036 21528 001 A 0303 Unitary Products Group 21 FIGURE 7 ROOF CURB DIMENSIONS...

Page 22: ...036 21528 001 A 0303 22 Unitary Products Group FIGURE 8 TYPICAL WIRING DIAGRAM 208 230 1 60 POWER SUPPLY...

Page 23: ...036 21528 001 A 0303 Unitary Products Group 23 FIGURE 9 TYPICAL WIRING DIAGRAM 230 3 60 POWER SUPPLY...

Page 24: ...036 21528 001 A 0303 24 Unitary Products Group FIGURE 10 TYPICAL WIRING DIAGRAM 460 3 60 POWER SUPPLY...

Page 25: ...l be provided to assure reliable transit of equipment overhead rig ging fork truck access and proper sealing on roof curb applications Base rails shall be removable when required to lower unit height...

Page 26: ...pressures C Unit shall contain a reliable demand defrost control to provide defrost The defrost control shall also have an X terminal to provide a 24 volt signal for room thermostat LED indication of...

Page 27: ...036 21528 001 A 0303 Unitary Products Group 27...

Page 28: ...001 A 0303 Copyright by Unitary Products Group 2003 All rights reserved Supersedes Nothing Unitary 5005 Norman Products York OK Group Drive 73069 This product was manufactured in a plant whose qualit...

Reviews: