background image

Page 23

Installation, Operation & Maintenance Manual ( IOPCKKS60220510C1)

4. 

If compressor contactor 1 is not pulled in, check for 24 volts 
at the coil. If 24 volts is present and compressor contactor 1 
is not pulled in, replace the contactor.

5. 

Failing the above, if voltage is supplied at compressor 
contactor 1, and it is pulled in, and the compressor still does 
not operate, replace the compressor.

6. 

If 24 volts is not present at compressor contactor, check for 
24 volts at the UCB terminal, C1. If 24 volts is present, check 
for loose wiring between C1 and the compressor contactor  
1.

7. 

If 24 volts is not present at the C1 terminal, check for 24 volts 
from the room thermostat at the UCB Y1 terminal. If 24 volts 
are not present at the UCB Y1 terminal, the UCB may have 
faulted. Check for 24 volts at the Y1 ECON terminal. If 24 volts 
is not present at Y1 “ECON”, the UCB has faulted. The UCB 
should de-energize all compressors on a loss of call for the 
first stage of cooling, i.e. a loss if 24 volts at the Y1 terminal.

8. 

If 24 volts are present at the UCB Y1 terminal, the compressor 
may be out due to an open high-pressure switch, low-
pressure switch, or freezestat. Check for 24 volts at the HPS1, 
LPS1, and FS1 terminals of the UCB. If a switch has opened, 
threshold be a voltage potential between the UCB terminals, 
e.g. if LPS1 has opened, there will be a 24- volt potential 
between the LPS1 terminals.\

9. 

If 24 volts is present at the UCB Y1 terminal and none of the 
protection switches have opened, the UCB may have locked 
out the compressor for repeat trips. The UCB should be 
flashing a code. If not, press and release the ALARMS button 
on the UCB. The UCB will flash the last five alarms on the LED. 
If the compressor is locked out, remove any call for cooling. 
This will reset any compressor lock outs.

* NOTE : While the above step will reset any lock outs, 
compressor # 2 will be held off for the ASCD, and compressor 
# 1 may be held off for a portion of the ASCD. See the next 
step.

10. 

If 24 volts is present at the UCB Y1 terminal and none of the 
switches are open and the compressor is not locked out, the 
UCB may have the compressor in an ASCD. Check the LED for 
an indication of an ASCD cycle. The ASCD should time out 
within 5 minutes. Press and release the TEST button to reset 
all ASCDs.

11. 

If 24 volts is present at the UCB Y1 terminal and the compressor 
is not out due to a protective switch trip, repeat trip lock 
out, or ASCD, the economizer terminals of the UCB may be 
improperly wired. Check for 24 volts at the Y1 “OUT” terminal 
of the UCB. If 24 volts is present, trace the wiring from Y1 
“OUT” for incorrect wiring. If 24 volts is not present at the Y1 
“OUT” terminal, the UCB must be replaced.

12. 

If none of the above corrected the error, test the integrity of 
the UCB. Disconnect the C1 terminal wire and jumper it to 
the Y1 terminal. DO NOT jump the Y1 to C1 terminals. If the 
compressor engages, has faulted.

13. 

If none of the above correct the error, replace the UCB.

UNIT FLASH CODES

Various flash codes are utilized by the unit control board (UCB) to 
aid in troubleshooting. Flash codes are distinguished by the short 
on and off cycle used (approximately 200 ms on and 200 ms off). 
To show normal operation, the control board flashes a 1 second 
on, 1 second off heartbeat during normal operation. This is to 
verify that the UCB is functioning correctly.

Do not confuse this with an error flash code. To prevent confusion, 
a 1-flash, flash code is not used. Current alarms are flashed on the 
UCB LED. Pressing and releasing the ALARMS button on the UCB 
can check the alarm history. The UCB will cycle through the last 
five (5) alarms, most recent to oldest, separating each alarm flash 
code by approximately 2 seconds.

In some cases, it may be necessary to “zero” the ASCD for the 
compressors in order to perform troubleshooting. To reset all 
ASCDs for one cycle, press and release the UCB TEST button once. 
See table 10, Unit Flash Codes.

1: These flash codes do not represent alarms

TABLE 10: UNIT FLASH CODES

Summary of Contents for 30 to 50 TR

Page 1: ...Installation Operation Maintenance Manual 60 Hz DMS Saber Series Air Cooled Packaged Air Conditioners 30 to 50 TR...

Page 2: ...onal safety 15 Use and Operation 16 Adherence to warnings 16 Staff training 16 Use of the unit 16 Recommended safety practices 17 Applicable standards of EEC machinery directive 17 OPERATION Sound pow...

Page 3: ...es and work gloves and follow all safety codes Use a quenching cloth and have a fire extinguisher available for all brazing operations INSPECTION As soon as a unit is received it should be inspected f...

Page 4: ...al and local safety codes Refer to Unit Application Data table If components are to be added to a unit to meet local codes they are to be installed at the dealer s and or the customer s expense Size o...

Page 5: ...ITS WEIGHT IS DISTRIBUTED EQUALLY ON ALL CABLES SO IT WILL LIFT EVENLY CLEARANCES All units require certain clearances for proper operation and service Installer must make provisions for adequate ven...

Page 6: ...Install a condensate drain line from the one inch FPT female connection on the unit to an open drain NOTE The condensate drain operates in a negative pressure in the cabinet The condensate drain line...

Page 7: ...ating with a short circuit capacity of 10K or more for the unit The switch must be separate from all other circuits Wire entry at knockout openings require conduit fittings to comply with local codes...

Page 8: ...incoming line connection phasing to obtain proper rotation Scroll compressors operate in only one direction If the scroll is drawing low amperage has similar suction and discharge pressures or produci...

Page 9: ...ts lbs Kg 3520 1600 3630 1650 3720 1691 4150 1886 Basic Unit Ratings ARI Conditions Heating Capacities Dimensions Motor size Filters Refrigerant Height of Comp s Hermetic Scroll 6 Pole Class F Insulat...

Page 10: ...DATA DMS 360 420 480 600 Notes 1 DMS 600 with 4 condenser fans 2 For economizer option add 800 mm to the unit length 3 For bag filter option add 800 mm to the unit length 4 When selecting the option o...

Page 11: ...280 725 875 555 1751 600 VAR 146 A2 1615 x 42mm 116 140 SPA 280 2 2517 x 35mm 280 725 875 555 1751 480 VAR 146 A2 1615 x 42mm 116 140 SPA 280 2 2517 x 35mm 280 725 875 540 1721 725 875 540 1721 420 VA...

Page 12: ...70 9 225 136 3 175 36 0 45 2 136 3 175 54 0 67 8 136 3 175 Voltage Minimum Circuit Amperes 3 1 160 0 220 V 3Ph 60 Hz 18 9 14 3 17 5 Maximum Fuse Breaker Size Compressors Condenser Fan Motors FLA Elect...

Page 13: ...65 820 6 20 868 6 84 916 7 50 964 8 22 1012 8 97 12500 5900 549 2 56 608 3 00 667 3 47 725 3 96 783 4 55 840 5 16 895 5 82 949 6 51 1000 7 23 1050 7 97 14000 6608 590 3 39 647 3 88 699 4 37 751 4 90 8...

Page 14: ...e Manual IOPCKKS60220510C1 ADDITIONAL PRESSURE DROPS The additional pressure losses should be calculated from the raph and ADDED along with the ESP External Static Pressure to calculate fan performanc...

Page 15: ...he conditioned space The job specifications may require that this balancing be done by someone other than the equipment installer WARNING FAILURE TO PROPERLY ADJUST THE TOTAL SYSTEM AIR QUANTITY CAN R...

Page 16: ...ower before opening the access doors 3 Warnings against coming into contact with electrical parts All warnings and signs regarding the units must be absolutely observed STAFF TRAINING The unit should...

Page 17: ...1 12100 2 1 2 8 Software Refer to IOM for details of Simplicity Programming UNI EN 12100 1 12100 2 1 3 2 Risk of breakup during operation operating conditions stated on the as built drawings frequenc...

Page 18: ...watts Table 8 Sound Power Levels DMS Saber Units Table 9 Sound Power Levels Standard Fans VOLT FREE CONTACT All Saber units are supplied with Volt free contact Refer to Electrical wiring schematic th...

Page 19: ...le stop the condenser fans Once the low pressure switch has been proven closed during the 30 second monitor period described above the UCB will monitor the low pressure limit switch for any openings I...

Page 20: ...d This limit is monitored regardless of unit operation status i e the limit is monitored at all times If the temperature limit opens three times within one hour it will lock on the indoor blower motor...

Page 21: ...el any thermostat calls and set the fan switch to AUTO Wait for the internal overload to reset Test again when cool 5 If blower contactor is not pulled in check for 24 volts at the contactor coil If 2...

Page 22: ...or 24 volts at the UCB terminal C2 If 24 volts are present check for loose wiring between C2 and the compressor contactor 7 If 24 volts is not present at the C2 terminal check for 24 volts from the ro...

Page 23: ...compressor 1 may be held off for a portion of the ASCD See the next step 10 If 24 volts is present at the UCB Y1 terminal and none of the switches are open and the compressor is not locked out the UC...

Page 24: ...mately 10 mm to 13 mm when pressed lightly with a finger EVERY SIX MONTHS In addition to the maintenance done every three months t The condenser coils should be cleaned by spraying water over it at lo...

Page 25: ...Page 25 Installation Operation Maintenance Manual IOPCKKS60220510C1...

Page 26: ...Page 26 Installation Operation Maintenance Manual IOPCKKS60220510C1...

Page 27: ...Page 27 Installation Operation Maintenance Manual IOPCKKS60220510C1...

Page 28: ...y aspect of our business York products are now a premier brand manufactured by Johnson Controls The acquisition of York gives us a unique insight into designing HVAC products that match your exact req...

Reviews: