Page 9
Installation, Operation & Maintenance Manual ( IOPCKKS60220510C1)
PRODUCT DATA
Table 4: Production Data
DMS
360
420
480
600
Btuh/W
10.3
10.9
8.7
8.7
MBh (kW)
344.6 ( 101 )
386.3 ( 113.2 )
462.9 ( 135.7 )
588 ( 172.3 )
hp (kW)
30.6 ( 22.8 )
31.5 ( 23.5 )
50.9 ( 38 )
69.7 ( 52 )
122.7 ( 36 )
122.7 ( 36 )
122.7 ( 36 )
122.7 ( 36 )
184.1 ( 54 )
184.1 ( 54 )
184.1 ( 54 )
184.1 ( 54 )
fpi (mm)
10 ( 2.5 )
14 ( 3.5 )
14 ( 3.5 )
14 ( 3.5 )
ft² (m²)
31.7 ( 2.9 )
31.7 ( 2.9 )
31.7 ( 2.9 )
38 (3.5 )
fpi (mm)
16 ( 4.0 )
12 ( 2.1 )
12 ( 2.1 )
12 ( 2.1 )
ft² (m²)
50.7 ( 4.7 )
50.7 ( 4.7 )
50.7 ( 4.7 )
50.7 ( 4.7 )
2
2
2
2
std
10 ( 7.5 )
10 ( 7.5 )
15 ( 11 )
15 ( 11 )
xtd
15 ( 11 )
15 ( 11 )
20 ( 50 )
20 ( 15 )
3
4
4
4
hp (kW)
1.5 ( 1.1 )
1.5 ( 1.1 )
1.5 ( 1.1 )
1.5 ( 1.1 )
3
4
4
4
3
3
3
4
3
3
3
4
lbs (kgs)
13.2 ( 6 )
24.2 ( 11 )
22 ( 10 )
15.4 ( 7 )
Weights
lbs (Kg)
3520 ( 1600 )
3630 ( 1650 )
3720 ( 1691 )
4150 ( 1886 )
Basic Unit
Ratings @ ARI Conditions
Heating Capacities
Dimensions
Motor size
Filters
Refrigerant
Height
# of Comp.s
Hermetic Scroll
6 Pole, Class F Insulation, Totally Enclosed Fan Cooled, IP 54, 1100 rpm
MBh(kW)
EER
Capacity
Compressor
Power Input
Option 1
Option 2
Enhanced Copper /Aluminium
R-22
Quantity
H X L X D- Qty
Type
No of Circuits
inches (mm)
Length
Width
Charge / Cir
4 Blade heavy duty Propeller Fan
4 Pole, Class F Insulation, Totally Enclosed Fan Cooled, IP 54, 1700 rpm
Forward Curved Centrifugal - DIDW
Enhanced Copper /Aluminium
Model
Fins
Area
Condenser Fan & Motor
Blower Fan & Motor
Motor
Size
Type
Type
Quantity
Motor Type
Evaporator Coil
Condenser Coil
Compressor
Tube / Fins
Tube
Area
69.9 (1776)
88 (2235)
205 (5207)
24 x 24 x 2 (610 x 610 x 50 ) - 6#
H X L X D- Qty
Fins
Fan Type
Fan Qty
Motor Type
hp (kW)