background image

Page 21

Installation, Operation & Maintenance Manual ( IOPCKKS60220510C1)

SHUT DOWN

1. 

Set the thermostat to highest temperature setting.

2. 

Turn off the electrical power to the unit.

BELT DRIVE BLOWER

All units have belt drive single speed blower motors. The variable 
pitch pulley on the blower motor can be adjusted to obtain the 
desired supply air CFM. For high static requirement (DMS 480 & 
600), fixed pitch pulleys will be provided.

TROUBLE SHOOTING

COOLING TROUBLE SHOOTING GUIDE

 

 

WARNING

TROUBLESHOOTING OF COMPONENTS MAY REQUIRE 
OPENING THE ELECTRICAL CONTROL BOX WITH THE 

 

POWER CONNECTED TO THE UNIT. USE EXTREME CARE 
WHEN WORKING WITH LIVE CIRCUITS! CHECK THE UNIT 
NAMEPLATE FOR THE CORRECT LINE VOLTAGE AND 
SET THE VOLTMETER TO THE CORRECT RANGE BEFORE 
MAKING ANY CONNECTIONS WITH LINE TERMINALS.

Troubleshooting of components may require opening the electrical 
control box with the power connected to the unit.  Use extreme 
care when working with live circuits! Check the unit nameplate for 
the correct line voltage and set the voltmeter to the correct range 
before making any connections with line terminals.

When not necessary, shut off  all electric power to the unit prior 
to any of the following  maintenance procedures so as to prevent 
personal injury.

 

 

CAUTION

LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN 
SERVICING CONTROLS. WIRING ERRORS CAN CAUSE 

 

IMPROPER AND DANGEROUS OPERATION, WHICH 
COULD CAUSE INJURY TO PERSON AND/OR DAMAGE 
UNIT  COMPONENTS. VERIFY PROPER OPERATION 
AFTER SERVICING.

* On calls for cooling, if the compressors are operating but 
the supply air blower motor does not energize after a short 
delay (the room thermostat fan switch is in the “AUTO” 
position).

1. 

Turn the thermostat fan switch to the ON position. If the 
supply air blower motor does not energize, go to Step 3.

2. 

If the blower motor runs with the fan switch in the ON position 
but will not run after the first compressor has energized 

when the fan switch is in the AUTO position, check the room 
thermostat for contact between R and G in the AUTO position 
during calls for cooling.

3. 

If the supply air blower motor does not energize when the fan 
switch is set to ON, check that line voltage is being supplied 
to the blower contactor, and that the contactor is pulled in. 
Check for loose wiring between the contactor and the supply 
air blower motor.

4. 

If blower contactor is pulled in and voltage is supplied to 
contactor, lightly touch the supply air blower motor housing. 
If it is hot, the motor may be off on internal protection. Cancel 
any thermostat calls and set the fan switch to AUTO. Wait for 
the internal overload to reset. Test again when cool.

5. 

If blower contactor is not pulled in, check for 24 volts at the 
contactor coil. If 24 volts are present but it is not pulled in, 
replace the contactor.

6. 

Failing the above, if there is line voltage supplied at contactor 
and it is pulled in, and the supply air blower motor still does 
not operate, replace the motor. 

7. 

If 24 volts is not present at blower contactor, check that 24 
volts is present at the UCB supply air blower motor terminal, 
“FAN”. If 24 volts is present at the FAN, check for loose wiring 
between the UCB and blower contactor.

8. 

If 24 volts is not present at the “FAN” terminal, check for 
24 volts from the room thermostat. If 24 volts are not 
present from the room thermostat, check for the following : 
a. Proper operation of the room thermostat (contact 
between R and G with the fan switch in the ON position 
and in the AUTO position during operation calls), 
b. Proper wiring between the room thermostat and the UCB, and 
c. Loose wiring from the room thermostat to the UCB.

9. 

If 24 volts is present at the room thermostat but not at the 
UCB, check for proper wiring between the thermostat and the 
UCB, i.e. that the thermostat G terminal is connected to the G 
terminal of the UCB, and for loose wiring.

10. 

If the thermostat and UCB are properly wired, replace the 
UCB.

On calls for cooling, the supply air blower motor is operating 
but compressor # 1 is not (the room thermostat fan switch is 
in the “AUTO” position).

1. 

If compressor # 1 does not energize on a call for cooling, 
check for line voltage at the compressor contactor 1, and that 
the contactor is pulled in. Check for loose wiring between the 
contactor and the compressor.

2. 

If compressor contactor 1 is pulled in and voltage is 
supplied, lightly touch the compressor housing. If it ishot, the 
compressor may be off on inherent protection. Cancel any 
calls for cooling and wait for the internal overload to reset. 
Test again when cool.

3. 

If compressor contactor 1 is not pulled in, check for 24 volts 
at the coil. If 24 volts are present and contactor is not pulled 
in, replace the contactor. 

4. 

Failing the above, if voltage is supplied at compressor 
contactor 1, it is pulled in, and the compressor still does not 
operate, replace the compressor. 

5. 

If 24 volts is not present at compressor contactor 1, check for 
24 volts at the UCB terminal, C1. If 24 volts is present, check 
for loose wiring between C1 and the compressor contactor.

6. 

If 24 volts is not present at the C1 terminal, check for 24 
volts from the room thermostat at the UCB Y1 terminal. If 24 
volts is not present from the room thermostat, check for the 
following : 

tWPMUTBUUIFUIFSNPTUBU:UFSNJOBM

 

Summary of Contents for 30 to 50 TR

Page 1: ...Installation Operation Maintenance Manual 60 Hz DMS Saber Series Air Cooled Packaged Air Conditioners 30 to 50 TR...

Page 2: ...onal safety 15 Use and Operation 16 Adherence to warnings 16 Staff training 16 Use of the unit 16 Recommended safety practices 17 Applicable standards of EEC machinery directive 17 OPERATION Sound pow...

Page 3: ...es and work gloves and follow all safety codes Use a quenching cloth and have a fire extinguisher available for all brazing operations INSPECTION As soon as a unit is received it should be inspected f...

Page 4: ...al and local safety codes Refer to Unit Application Data table If components are to be added to a unit to meet local codes they are to be installed at the dealer s and or the customer s expense Size o...

Page 5: ...ITS WEIGHT IS DISTRIBUTED EQUALLY ON ALL CABLES SO IT WILL LIFT EVENLY CLEARANCES All units require certain clearances for proper operation and service Installer must make provisions for adequate ven...

Page 6: ...Install a condensate drain line from the one inch FPT female connection on the unit to an open drain NOTE The condensate drain operates in a negative pressure in the cabinet The condensate drain line...

Page 7: ...ating with a short circuit capacity of 10K or more for the unit The switch must be separate from all other circuits Wire entry at knockout openings require conduit fittings to comply with local codes...

Page 8: ...incoming line connection phasing to obtain proper rotation Scroll compressors operate in only one direction If the scroll is drawing low amperage has similar suction and discharge pressures or produci...

Page 9: ...ts lbs Kg 3520 1600 3630 1650 3720 1691 4150 1886 Basic Unit Ratings ARI Conditions Heating Capacities Dimensions Motor size Filters Refrigerant Height of Comp s Hermetic Scroll 6 Pole Class F Insulat...

Page 10: ...DATA DMS 360 420 480 600 Notes 1 DMS 600 with 4 condenser fans 2 For economizer option add 800 mm to the unit length 3 For bag filter option add 800 mm to the unit length 4 When selecting the option o...

Page 11: ...280 725 875 555 1751 600 VAR 146 A2 1615 x 42mm 116 140 SPA 280 2 2517 x 35mm 280 725 875 555 1751 480 VAR 146 A2 1615 x 42mm 116 140 SPA 280 2 2517 x 35mm 280 725 875 540 1721 725 875 540 1721 420 VA...

Page 12: ...70 9 225 136 3 175 36 0 45 2 136 3 175 54 0 67 8 136 3 175 Voltage Minimum Circuit Amperes 3 1 160 0 220 V 3Ph 60 Hz 18 9 14 3 17 5 Maximum Fuse Breaker Size Compressors Condenser Fan Motors FLA Elect...

Page 13: ...65 820 6 20 868 6 84 916 7 50 964 8 22 1012 8 97 12500 5900 549 2 56 608 3 00 667 3 47 725 3 96 783 4 55 840 5 16 895 5 82 949 6 51 1000 7 23 1050 7 97 14000 6608 590 3 39 647 3 88 699 4 37 751 4 90 8...

Page 14: ...e Manual IOPCKKS60220510C1 ADDITIONAL PRESSURE DROPS The additional pressure losses should be calculated from the raph and ADDED along with the ESP External Static Pressure to calculate fan performanc...

Page 15: ...he conditioned space The job specifications may require that this balancing be done by someone other than the equipment installer WARNING FAILURE TO PROPERLY ADJUST THE TOTAL SYSTEM AIR QUANTITY CAN R...

Page 16: ...ower before opening the access doors 3 Warnings against coming into contact with electrical parts All warnings and signs regarding the units must be absolutely observed STAFF TRAINING The unit should...

Page 17: ...1 12100 2 1 2 8 Software Refer to IOM for details of Simplicity Programming UNI EN 12100 1 12100 2 1 3 2 Risk of breakup during operation operating conditions stated on the as built drawings frequenc...

Page 18: ...watts Table 8 Sound Power Levels DMS Saber Units Table 9 Sound Power Levels Standard Fans VOLT FREE CONTACT All Saber units are supplied with Volt free contact Refer to Electrical wiring schematic th...

Page 19: ...le stop the condenser fans Once the low pressure switch has been proven closed during the 30 second monitor period described above the UCB will monitor the low pressure limit switch for any openings I...

Page 20: ...d This limit is monitored regardless of unit operation status i e the limit is monitored at all times If the temperature limit opens three times within one hour it will lock on the indoor blower motor...

Page 21: ...el any thermostat calls and set the fan switch to AUTO Wait for the internal overload to reset Test again when cool 5 If blower contactor is not pulled in check for 24 volts at the contactor coil If 2...

Page 22: ...or 24 volts at the UCB terminal C2 If 24 volts are present check for loose wiring between C2 and the compressor contactor 7 If 24 volts is not present at the C2 terminal check for 24 volts from the ro...

Page 23: ...compressor 1 may be held off for a portion of the ASCD See the next step 10 If 24 volts is present at the UCB Y1 terminal and none of the switches are open and the compressor is not locked out the UC...

Page 24: ...mately 10 mm to 13 mm when pressed lightly with a finger EVERY SIX MONTHS In addition to the maintenance done every three months t The condenser coils should be cleaned by spraying water over it at lo...

Page 25: ...Page 25 Installation Operation Maintenance Manual IOPCKKS60220510C1...

Page 26: ...Page 26 Installation Operation Maintenance Manual IOPCKKS60220510C1...

Page 27: ...Page 27 Installation Operation Maintenance Manual IOPCKKS60220510C1...

Page 28: ...y aspect of our business York products are now a premier brand manufactured by Johnson Controls The acquisition of York gives us a unique insight into designing HVAC products that match your exact req...

Reviews: