background image

Page 19

Installation, Operation & Maintenance Manual ( IOPCKKS60220510C1)

When the thermostat calls for 2nd stage of cooling low voltage 
control circuit from R to Y2 is completed, compressor 2 is 
energized, provided it has not been locked out.

For third stage of cooling, the low voltage control circuit from”R” 
to “Y3” is completed. Compressor # 3, condenser fan motor 3 & 
4* are energized, if there is an initial call for 3 stages of cooling, 
the UCB will delay energizing compressor 2 & 3 by 30 seconds 
each. Once the thermostat has been satisfied it will de-energize 
Y1, Y2 & Y3.

When the thermostat calls for fourth stage of cooling (for 50TR 
only), the low voltage control circuit from “R” to “Y4” is completed, 
compressor # 4 is energized. If there is an initial call for 4 stages 
of cooling, the UCB will delay energizing compressor # 2, 3 & 4 by 
30 seconds each. Once the thermostat has been satisfied it will 
de-energize Y1, Y2, and Y3 & Y4.

NOTE:
Condenser fan motors are 3 only in case of 30 TR models.

If the compressors have satisfied their minimum run times, the 
compressors and condenser fans are de-energized. Otherwise, 
the unit operates each cooling system until the minimum run 
times for the compressors have been completed. Upon the final 
compressor de-energizing, the blower is stopped following the 
elapse of the fan off delay for cooling.

To be available, a compressor must not be locked out due to a high 
or low pressure switch or freezestat trip and the anti short cycle 
delay (ASCD) must have elapsed.

COOLING OPERATION ERRORS

Each cooling system is monitored for operation outside of the 
intended parameters. Errors are handled as described below. All 
system errors override minimum run times for compressors.

HIGH PRESSURE LIMIT SWITCH

During cooling operation, if a high pressure limit switch opens, 
the UCB will de-energize the associated compressor, initiate the 
ASCD (anti short cycle delay), and, if the other compressors are 
idle, stop the condenser fans. If the call for cooling is still present 
at the conclusion of the ASCD, the UCB will re-energize the halted 
compressors.

Should a high pressure switch open three times within two hours 
of operation, the UCB will lock out the associated compressors and 
flash a code (see Table 11). If the other compressors are inactive, 
the condenser fans will be de-energized.

LOW PRESSURE LIMIT SWITCH

The low pressure limit switch is not monitored during the initial 
30 seconds of a cooling system’s operation. For the following 30 
seconds, the UCB will monitor the low pressure switch to ensure 
it closes. If the low pressure switch fails to close after the 30 
second monitoring phase, the UCB will de-energize the associated 
compressor, initiate the ASCD, and, if the other compressors are 
idle, stop the condenser fans.

Once the low pressure switch has been proven (closed during 
the 30 second monitor period described above), the UCB will 
monitor the low pressure limit switch for any openings. If the low 
pressure switch opens for greater than 5 seconds, the UCB will 
de-energize the associated compressor, initiate the ASCD, and, 
if the other compressor is idle, stop the condenser fans. If the 
call for cooling is still present at the conclusion of the ASCD, the 
UCB will re-energize the halted compressor. Should a low pressure 
switch open three times within one hour of operation, the UCB 
will lock out the associated compressor and flash a code (Table 
11). If the other compressor is inactive, the condenser fans will be 
de-energized.

FREEZESTAT

During cooling operation, if a freezestat opens, the UCB will de-
energize the associated compressor, initiate the ASCD, and, if the 
other compressor is idle, stop the condenser fans. If the call for 
cooling is still present at the conclusion of the ASCD, the UCB will 
reenergize the halted compressor. Should a freezestat open three 
times within two hours of  operation, the UCB will lock out the 
associated compressor  and flash a code (Table 11). If the other 
compressor is inactive, the condenser fans will be de-energized.

LOW AMBIENT COOLING (OPTIONAL)

To determine when to operate in low ambient mode, the UCB 
has a pair of terminals connected to a temperature activated 
switch set at 50°F. When the low ambient switch is closed and the 
thermostat is calling for cooling, the UCB will operate  in the low 
ambient mode.

Low ambient mode operates the compressors in this manner: 
10 minutes on, 5 minutes off. The indoor blower is operated 
throughout the cycle. The 5 minute off period is  necessary to 
defrost the indoor coil. Low ambient mode  always begins with 
compressor operation. Compressor minimum run time may extend 
the minutes of compressor operation.

The defrost cycle will begin immediately following the elapse of the 
minimum run time. When operating in low ambient mode, the UCB 
will not lockout the compressors due to a  freezestat trip. However, 
a freezestat trip will de-energize the associated compressor. If the 
call for cooling is still present at the end of the ASCD and the 
freezestat has closed, the unit will resume operation.

SAFETY CONTROLS

The unit control board monitors the following inputs for each 
cooling system :

1. 

A suction line freezestat to protect against low evaporator 
temperatures due to a low air flow or a low Installation, return 
air temperature, (opens at 26 ± 5°F and resets at 38 ± 5°F).

2. 

A high pressure switch to protect against excessive discharge 
pressures due to a blocked condenser coil or a condenser 
motor failure, (opens at 415 ± 15 psig and resets at 280 ± 15 
psig).

3. 

A low pressure switch to protect against loss of refrigerant 
charge, (opens at 35 ± 5 psig and resets at 60  ± 5 psig). The 
above pressure switches are hard  soldered to the unit.

Summary of Contents for 30 to 50 TR

Page 1: ...Installation Operation Maintenance Manual 60 Hz DMS Saber Series Air Cooled Packaged Air Conditioners 30 to 50 TR...

Page 2: ...onal safety 15 Use and Operation 16 Adherence to warnings 16 Staff training 16 Use of the unit 16 Recommended safety practices 17 Applicable standards of EEC machinery directive 17 OPERATION Sound pow...

Page 3: ...es and work gloves and follow all safety codes Use a quenching cloth and have a fire extinguisher available for all brazing operations INSPECTION As soon as a unit is received it should be inspected f...

Page 4: ...al and local safety codes Refer to Unit Application Data table If components are to be added to a unit to meet local codes they are to be installed at the dealer s and or the customer s expense Size o...

Page 5: ...ITS WEIGHT IS DISTRIBUTED EQUALLY ON ALL CABLES SO IT WILL LIFT EVENLY CLEARANCES All units require certain clearances for proper operation and service Installer must make provisions for adequate ven...

Page 6: ...Install a condensate drain line from the one inch FPT female connection on the unit to an open drain NOTE The condensate drain operates in a negative pressure in the cabinet The condensate drain line...

Page 7: ...ating with a short circuit capacity of 10K or more for the unit The switch must be separate from all other circuits Wire entry at knockout openings require conduit fittings to comply with local codes...

Page 8: ...incoming line connection phasing to obtain proper rotation Scroll compressors operate in only one direction If the scroll is drawing low amperage has similar suction and discharge pressures or produci...

Page 9: ...ts lbs Kg 3520 1600 3630 1650 3720 1691 4150 1886 Basic Unit Ratings ARI Conditions Heating Capacities Dimensions Motor size Filters Refrigerant Height of Comp s Hermetic Scroll 6 Pole Class F Insulat...

Page 10: ...DATA DMS 360 420 480 600 Notes 1 DMS 600 with 4 condenser fans 2 For economizer option add 800 mm to the unit length 3 For bag filter option add 800 mm to the unit length 4 When selecting the option o...

Page 11: ...280 725 875 555 1751 600 VAR 146 A2 1615 x 42mm 116 140 SPA 280 2 2517 x 35mm 280 725 875 555 1751 480 VAR 146 A2 1615 x 42mm 116 140 SPA 280 2 2517 x 35mm 280 725 875 540 1721 725 875 540 1721 420 VA...

Page 12: ...70 9 225 136 3 175 36 0 45 2 136 3 175 54 0 67 8 136 3 175 Voltage Minimum Circuit Amperes 3 1 160 0 220 V 3Ph 60 Hz 18 9 14 3 17 5 Maximum Fuse Breaker Size Compressors Condenser Fan Motors FLA Elect...

Page 13: ...65 820 6 20 868 6 84 916 7 50 964 8 22 1012 8 97 12500 5900 549 2 56 608 3 00 667 3 47 725 3 96 783 4 55 840 5 16 895 5 82 949 6 51 1000 7 23 1050 7 97 14000 6608 590 3 39 647 3 88 699 4 37 751 4 90 8...

Page 14: ...e Manual IOPCKKS60220510C1 ADDITIONAL PRESSURE DROPS The additional pressure losses should be calculated from the raph and ADDED along with the ESP External Static Pressure to calculate fan performanc...

Page 15: ...he conditioned space The job specifications may require that this balancing be done by someone other than the equipment installer WARNING FAILURE TO PROPERLY ADJUST THE TOTAL SYSTEM AIR QUANTITY CAN R...

Page 16: ...ower before opening the access doors 3 Warnings against coming into contact with electrical parts All warnings and signs regarding the units must be absolutely observed STAFF TRAINING The unit should...

Page 17: ...1 12100 2 1 2 8 Software Refer to IOM for details of Simplicity Programming UNI EN 12100 1 12100 2 1 3 2 Risk of breakup during operation operating conditions stated on the as built drawings frequenc...

Page 18: ...watts Table 8 Sound Power Levels DMS Saber Units Table 9 Sound Power Levels Standard Fans VOLT FREE CONTACT All Saber units are supplied with Volt free contact Refer to Electrical wiring schematic th...

Page 19: ...le stop the condenser fans Once the low pressure switch has been proven closed during the 30 second monitor period described above the UCB will monitor the low pressure limit switch for any openings I...

Page 20: ...d This limit is monitored regardless of unit operation status i e the limit is monitored at all times If the temperature limit opens three times within one hour it will lock on the indoor blower motor...

Page 21: ...el any thermostat calls and set the fan switch to AUTO Wait for the internal overload to reset Test again when cool 5 If blower contactor is not pulled in check for 24 volts at the contactor coil If 2...

Page 22: ...or 24 volts at the UCB terminal C2 If 24 volts are present check for loose wiring between C2 and the compressor contactor 7 If 24 volts is not present at the C2 terminal check for 24 volts from the ro...

Page 23: ...compressor 1 may be held off for a portion of the ASCD See the next step 10 If 24 volts is present at the UCB Y1 terminal and none of the switches are open and the compressor is not locked out the UC...

Page 24: ...mately 10 mm to 13 mm when pressed lightly with a finger EVERY SIX MONTHS In addition to the maintenance done every three months t The condenser coils should be cleaned by spraying water over it at lo...

Page 25: ...Page 25 Installation Operation Maintenance Manual IOPCKKS60220510C1...

Page 26: ...Page 26 Installation Operation Maintenance Manual IOPCKKS60220510C1...

Page 27: ...Page 27 Installation Operation Maintenance Manual IOPCKKS60220510C1...

Page 28: ...y aspect of our business York products are now a premier brand manufactured by Johnson Controls The acquisition of York gives us a unique insight into designing HVAC products that match your exact req...

Reviews: