Installation, Operation & Maintenance Manual ( IOPCKKS60220510C1)
PRODUCT NOMENCLATURE
INSTALLATION
Read these instructions before continuing this appliance
installation. This is an outdoor combination heating and cooling
unit. The installer must assure that these instructions are made
available to the consumer and with instructions to retain them for
future reference.
LIMITATIONS
These units must be installed in accordance with the applicable
national and local safety codes. (Refer to Unit Application Data
table).
If components are to be added to a unit to meet local codes, they
are to be installed at the dealer’s and/or the customer’s expense.
Size of unit for proposed installation should be based on heat loss/
heat gain calculation.
DMS-360
DMS-420
DMS-480
DMS-600
220V/3Ph/60Hz
380V/3Ph/60Hz
460V/3Ph/60Hz
Supply Airflow Rate (min/max)
cfm
9500/14000
10500/15000
12500/17000
14000/19000
On-Coil Wet Bulb Temperature (min/max)
°F
Ambient Air Temperature (min/max)
°F
Voltage Variation (min/max)
Unit Model Number
57/72
50/125 (30/125 with Low Ambient Option)
180/253
342/418
414/506
Table 1: Unit Application Data