background image

035-15713-003 REV. A (0500)

Unitary Products Group

5

INSULATION OF VAPOR LINE

Insulate vapor line with 3/8" (or that required by local code)
closed cell insulation.
Slide tubing insulation onto the vapor line so that it is covered
completely from the indoor coil to the outdoor unit. Be sure
that the tubing is capped before sliding on insulation.
It is not necessary to insulate the liquid line.

NOTE:  

In areas of extreme temperatures and humidity,

additional insulation may be required to prevent
excessive condensation and loss of capacity.       

Do not insulate liquid line and vapor line together. Liquid line
should not be in contact with the vapor line. See Figure 3.

RE-ASSEMBLING, BRAZING AND CLEANING OF 
JOINT CONNECTIONS

Remove the Schrader Valve cores from the service valves.
Remove the plugs from the service valve field tubing connec-
tions. Clean the joints to be brazed.

NOTE:  

Do not overheat the connection to be brazed as this

can cause improper flow of solder, resulting in a
weak and leaking joint. Never apply heat directly to
face of fitting. Do not heat solder by direct contact
with flame of the torch.

When brazing copper tubing it is very important to preheat
the entire joint before applying the solder. This is done by
sweeping the flame steadily and evenly around the fitting, to
bring both fitting and tubing up to equal temperature before
applying the solder.

Reassemble groups of tubing and fittings, brazing several
joints instead of one joint at a time. This reduces the chance
for error in the alignment of the assembly. Replace Schrader
Valve cores. DO NOT OPEN SERVICE VALVES AT THIS
TIME.
Clean joint connection immediately after brazing with wet rag.

REFRIGERANT LINE SUPPORT

Refrigerant lines should be supported in a way that no dips or
sags occur. We recommend four feet between supports. If
refrigerant lines are to be attached to the home structure,
care should be taken to eliminate the transmission of vibra-
tions. Attach the refrigerant lines to the indoor coil first.
Remove plugs from the indoor coil, then clean joints to be
brazed. Braze refrigerant lines to the indoor coil. Attach
refrigerant lines to the outdoor unit.

CHARGING AND LEAK TESTING

On systems with or without service valves the refrigerant
should be recovered or recycled in accordance with EPA reg-
ulations. In some cases this may require putting piercing
valves on both the high and low sides of the system.

When recovering refrigerant from a system, with a burnout,
follow a safe procedure due to possible contamination.

Contaminated refrigerant must be recovered and returned to
the local refrigeration supply house for proper disposition.

TOTAL LINE LENGTH

For systems with total line length exceeding 50 feet, see
APPLICATION DATA, 690.01-AD1V(1296) and worksheet
690.01-AD1.1V(791) General Piping Recommendations and
“Refrigerant Line Length” for vapor and liquid line sizing, cali-
bration of liquid line pressure loss or gain, determination of
vapor line velocity, elevation limitations, orifice connections,
system charging, traps, etc.
Total line lengths are limited to 75 feet due to the storage
capacity of the accumulator. Systems with total line lengths
over 50 feet must be provided with:

Low Voltage Start Kit.

Elevation differences are limited to:

Indoor above outdoor. . . .  50 ft.
Outdoor above indoor  . . .  50 ft.

Systems with liquid line pressure loss or gain greater than 11
psi must be provided with corrected orifice size.

 FIGURE 3 : 

INSULATION OF VAPOR LINE

When using hard solder, an inert gas such as dry
nitrogen must be introduced and permitted to flow
through tubing during brazing to displace air and
prevent oxidation.

DO NOT vent refrigerant to the outdoors.

Avoid getting the refrigerant in the eyes or on the
skin.

Summary of Contents for 10 Seer

Page 1: ...TATS 4 INDOOR UNITS 4 REFRIGERANT LINE SWEAT FIT 4 INSULATION OF VAPOR LINE 5 RE ASSEMBLING BRAZING AND CLEANING OF JOINT CONNECTIONS 5 REFRIGERANT LINE SUPPORT 5 CHARGING AND LEAK TESTING 5 TOTAL LIN...

Page 2: ...nd in accordance with the recommendations made by the National Board of Fire Underwriters Limitations for the indoor unit coil and appropriate accesso ries must also be observed The outdoor unit must...

Page 3: ...rom the coil can reduce capacity loss due to wind chill effect Provide ample clearance from shrubs to allow adequate air to pass across the outdoor coil without leaves or branches being pulled into th...

Page 4: ...y important when setting up a refrigeration system and need to be followed completely to insure that a strong flexible and leak tight system is obtained The installation of the copper refrigerant tubi...

Page 5: ...r sags occur We recommend four feet between supports If refrigerant lines are to be attached to the home structure care should be taken to eliminate the transmission of vibra tions Attach the refriger...

Page 6: ...t leaks Replace valve cap finger tight then tighten an additional 1 6 of a turn with a wrench using a back up wrench on the valve body OIL TRAPPING When the outdoor unit is above the indoor coil oil t...

Page 7: ...data sheet Do not use any line sets other than those shown 2 Copper tubing will work harden a The pre charged tubing should be handled carefully b Do not bend or work the tubing any more than nec essa...

Page 8: ...oil b Remove plugs and caps from connections c Check that the rubber seals in connection ends are intact d Be sure surfaces are clean e Lubricate the rubber seals with clean refrigerant oil and make c...

Page 9: ...must include a disconnect switch located within sight of the outdoor unit 2 Use the correct size fuse or circuit breaker as listed on the unit rating plate and data sheet If using nonmetallic sheathe...

Page 10: ...he low voltage junction box See Figures 10 11 12 2 Using wire nuts connect the low voltage wiring within the low voltage box 3 A minimum of 19 AWG wire must be used in connecting the low voltage contr...

Page 11: ...035 15713 003 REV A 0500 Unitary Products Group 11 FIGURE 13 DEMAND DEFROST BOARD 14 SEER FIGURE 14 TIME TEMPERATURE DEFROST BOARD 10 12 SEER...

Page 12: ...035 15713 003 REV A 0500 12 Unitary Products Group FIGURE 15 TYPICAL RESIDENTIAL AIR HANDLER FIGURE 16 TYPICAL MANUFACTURED HOUSING INSTALLATION...

Page 13: ...power to the transformer for at least two seconds TIME TEMPERATURE DEFROST The defrost control is a time temp control which includes a field selectable white tap located at board edge time period bet...

Page 14: ...AND DEFROST The test pins labeled speed up and defrost are provided to aid in field servicing of the heat pump See Figure 14 The pins are designed to be temporarily shorted together either by a screwd...

Page 15: ...035 15713 003 REV A 0500 Unitary Products Group 15 FIGURE 18 FLOW DIAGRAM 060 10 SEER FIGURE 19 FLOW DIAGRAM 024 THRU 048 14 SEER...

Page 16: ...er temperature pulls the liquid into the tank cavity and out of circulation within the system All R 22 likes a nice cool place to rest The net effect is that in cooling mode the system is using the wh...

Reviews: