background image

Subject to change without notice. Printed in U.S.A.

035-15713-003 REV. A (0500)

Copyright

 ©

 by York International Corp. 2000. All rights reserved.

Supersedes:035-15713-402 REV. C (0400)

Unitary

5005

Norman

Product

York

OK

Group

Drive

73069

INSTALLER

After installation is complete, place unit data sheet and instal-
lation instructions in customer packet and give to home
owner.

COMPENSATOR TANK FUNCTION

COOLING MODE:

In the cooling mode the state of the R-22 flowing through the
center tube (7/8") is hot superheated discharge gas. The R-
22 liquid in the tank is at a lower temperature than the super-
heated gas as it has been through the condensing coil and
has had heat removed. The higher temperature of the dis-
charge gas drives the liquid out of the cavity and into circula-
tion in the system.

HEATING MODE:

In the heating mode the state of the R-22 flowing through the
center tube (7/8") is cool superheated suction gas. The R-22
liquid in the tank is at a higher temperature than the suction
gas passing through the center tube. This cooler temperature
pulls the liquid into the tank cavity and out of circulation within
the system. (All R-22 likes a nice cool place to rest.)

The net effect is that in cooling mode, the system is using the
whole R-22 charge as marked on the rating plate. In heating
mode, the system is using 1.5 to 3 lbs. less charge depend-
ing upon the size of the tank. Giving optimized system perfor-
mance for both cooling and heating.

OPTIONAL OUTDOOR THERMOSTAT

The function of the outdoor thermostat kit is to prevent unnec-
essary use of auxiliary electric heat. At temperature above
the setting of the outdoor thermostat, the electric heat is
locked out and all of the heat is provided by the heat pump.
The setting or the outdoor thermostat is important and is ide-
ally selected at the home “balance point”, when the heat
pump capacity is equal to the heat loss of the home. See
instructions packed with these kits.

NOTE:  

 

All installations of this heat pump in Manu-

factured Homes built per HUD standards
SHALL have an outdoor thermostat
installed at the time of installation by the
installer. In accordance with HUD std.
3280.714 (a) (1) (ii). Outdoor thermostat,
Part number 3024-6881/D shall be used and
should be ordered at your nearest UPG
Parts Source

.

Summary of Contents for 10 Seer

Page 1: ...TATS 4 INDOOR UNITS 4 REFRIGERANT LINE SWEAT FIT 4 INSULATION OF VAPOR LINE 5 RE ASSEMBLING BRAZING AND CLEANING OF JOINT CONNECTIONS 5 REFRIGERANT LINE SUPPORT 5 CHARGING AND LEAK TESTING 5 TOTAL LIN...

Page 2: ...nd in accordance with the recommendations made by the National Board of Fire Underwriters Limitations for the indoor unit coil and appropriate accesso ries must also be observed The outdoor unit must...

Page 3: ...rom the coil can reduce capacity loss due to wind chill effect Provide ample clearance from shrubs to allow adequate air to pass across the outdoor coil without leaves or branches being pulled into th...

Page 4: ...y important when setting up a refrigeration system and need to be followed completely to insure that a strong flexible and leak tight system is obtained The installation of the copper refrigerant tubi...

Page 5: ...r sags occur We recommend four feet between supports If refrigerant lines are to be attached to the home structure care should be taken to eliminate the transmission of vibra tions Attach the refriger...

Page 6: ...t leaks Replace valve cap finger tight then tighten an additional 1 6 of a turn with a wrench using a back up wrench on the valve body OIL TRAPPING When the outdoor unit is above the indoor coil oil t...

Page 7: ...data sheet Do not use any line sets other than those shown 2 Copper tubing will work harden a The pre charged tubing should be handled carefully b Do not bend or work the tubing any more than nec essa...

Page 8: ...oil b Remove plugs and caps from connections c Check that the rubber seals in connection ends are intact d Be sure surfaces are clean e Lubricate the rubber seals with clean refrigerant oil and make c...

Page 9: ...must include a disconnect switch located within sight of the outdoor unit 2 Use the correct size fuse or circuit breaker as listed on the unit rating plate and data sheet If using nonmetallic sheathe...

Page 10: ...he low voltage junction box See Figures 10 11 12 2 Using wire nuts connect the low voltage wiring within the low voltage box 3 A minimum of 19 AWG wire must be used in connecting the low voltage contr...

Page 11: ...035 15713 003 REV A 0500 Unitary Products Group 11 FIGURE 13 DEMAND DEFROST BOARD 14 SEER FIGURE 14 TIME TEMPERATURE DEFROST BOARD 10 12 SEER...

Page 12: ...035 15713 003 REV A 0500 12 Unitary Products Group FIGURE 15 TYPICAL RESIDENTIAL AIR HANDLER FIGURE 16 TYPICAL MANUFACTURED HOUSING INSTALLATION...

Page 13: ...power to the transformer for at least two seconds TIME TEMPERATURE DEFROST The defrost control is a time temp control which includes a field selectable white tap located at board edge time period bet...

Page 14: ...AND DEFROST The test pins labeled speed up and defrost are provided to aid in field servicing of the heat pump See Figure 14 The pins are designed to be temporarily shorted together either by a screwd...

Page 15: ...035 15713 003 REV A 0500 Unitary Products Group 15 FIGURE 18 FLOW DIAGRAM 060 10 SEER FIGURE 19 FLOW DIAGRAM 024 THRU 048 14 SEER...

Page 16: ...er temperature pulls the liquid into the tank cavity and out of circulation within the system All R 22 likes a nice cool place to rest The net effect is that in cooling mode the system is using the wh...

Reviews: