background image

035-15713-003 REV. A (0500)

Unitary Products Group

3

Locate the outdoor unit near enough to the indoor coil vicinity
to eliminate lengthy refrigerant line runs. Do not locate the
outdoor unit so it discharges air under eaves or gutters. Rain
or snow melt-off should not be able to run off a roof and down
upon the unit. Be sure vents are not located upwind from the
outdoor unit.
A minimum clearance of 18 inches is required for service at
the control panel and compressor compartments access. A
10 inch clearance is required for the air inlet to the outdoor
coil around the perimeter of the unit. The air discharge of the
unit requires a 60 inch clearance between the top of the unit
and any obstruction. See Figure 1.
The length of the refrigerant tubing, between the outdoor unit
and indoor coil, should be as short as possible to avoid
capacity and efficiency loss. Excessive spacing of the out-
door unit from the home can lead to the refrigerant lines
being restricted by trampling or by being punctured by lawn
mowers. Locate the outdoor unit away from bedroom win-
dows or other rooms where sound might be objectionable.
Adverse effects of prevailing winds, blowing snow or sleet
onto the outdoor coil can be eliminated by placing the outdoor
unit where the wind does not blow across the unit. Trees,
shrubs, corners of buildings and fences standing off from the
coil can reduce capacity loss due to wind chill effect.

Provide ample clearance from shrubs to allow adequate air to
pass across the outdoor coil without leaves or branches
being pulled into the coil. The outdoor unit may never go into
the defrost cycle, even with minor frost build up, during the
daytime in some areas of the United States if it is placed on
the south side of the residence with no shade. However, the
heat pump may lose some efficiency at the south side loca-
tion with no shade during the summer while trying to cool the
residence.
Consideration should be given to the distance and routing of
electrical service that would have to be run to connect the
outdoor unit.
It is recommended the outdoor unit be mounted upon a solid
base that will not shift or settle. Top of base should be two
inches above grade. This allows enough height for normal
defrost ice build up below the unit in freezing weather.
Thought should be given to water drainage away from the
outdoor unit in summer and when the defrost ice melts on
warmer winter days. Drain holes in the base pan must be
kept clear.
In areas where snowfall is significant, the height of the unit
base above grade should be two to three inches higher than
the anticipated snowfall. This clearance is required to provide
ample drainage during the defrosting of the outdoor coil. Soil
grading around the heat pump should provide drainage away
from the unit to prevent slippery conditions that may cause
personal injury. See Figure 2.

 FIGURE 1 : 

TYPICAL RESIDENTIAL OUTDOOR UNIT LOCATION

Summary of Contents for 10 Seer

Page 1: ...TATS 4 INDOOR UNITS 4 REFRIGERANT LINE SWEAT FIT 4 INSULATION OF VAPOR LINE 5 RE ASSEMBLING BRAZING AND CLEANING OF JOINT CONNECTIONS 5 REFRIGERANT LINE SUPPORT 5 CHARGING AND LEAK TESTING 5 TOTAL LIN...

Page 2: ...nd in accordance with the recommendations made by the National Board of Fire Underwriters Limitations for the indoor unit coil and appropriate accesso ries must also be observed The outdoor unit must...

Page 3: ...rom the coil can reduce capacity loss due to wind chill effect Provide ample clearance from shrubs to allow adequate air to pass across the outdoor coil without leaves or branches being pulled into th...

Page 4: ...y important when setting up a refrigeration system and need to be followed completely to insure that a strong flexible and leak tight system is obtained The installation of the copper refrigerant tubi...

Page 5: ...r sags occur We recommend four feet between supports If refrigerant lines are to be attached to the home structure care should be taken to eliminate the transmission of vibra tions Attach the refriger...

Page 6: ...t leaks Replace valve cap finger tight then tighten an additional 1 6 of a turn with a wrench using a back up wrench on the valve body OIL TRAPPING When the outdoor unit is above the indoor coil oil t...

Page 7: ...data sheet Do not use any line sets other than those shown 2 Copper tubing will work harden a The pre charged tubing should be handled carefully b Do not bend or work the tubing any more than nec essa...

Page 8: ...oil b Remove plugs and caps from connections c Check that the rubber seals in connection ends are intact d Be sure surfaces are clean e Lubricate the rubber seals with clean refrigerant oil and make c...

Page 9: ...must include a disconnect switch located within sight of the outdoor unit 2 Use the correct size fuse or circuit breaker as listed on the unit rating plate and data sheet If using nonmetallic sheathe...

Page 10: ...he low voltage junction box See Figures 10 11 12 2 Using wire nuts connect the low voltage wiring within the low voltage box 3 A minimum of 19 AWG wire must be used in connecting the low voltage contr...

Page 11: ...035 15713 003 REV A 0500 Unitary Products Group 11 FIGURE 13 DEMAND DEFROST BOARD 14 SEER FIGURE 14 TIME TEMPERATURE DEFROST BOARD 10 12 SEER...

Page 12: ...035 15713 003 REV A 0500 12 Unitary Products Group FIGURE 15 TYPICAL RESIDENTIAL AIR HANDLER FIGURE 16 TYPICAL MANUFACTURED HOUSING INSTALLATION...

Page 13: ...power to the transformer for at least two seconds TIME TEMPERATURE DEFROST The defrost control is a time temp control which includes a field selectable white tap located at board edge time period bet...

Page 14: ...AND DEFROST The test pins labeled speed up and defrost are provided to aid in field servicing of the heat pump See Figure 14 The pins are designed to be temporarily shorted together either by a screwd...

Page 15: ...035 15713 003 REV A 0500 Unitary Products Group 15 FIGURE 18 FLOW DIAGRAM 060 10 SEER FIGURE 19 FLOW DIAGRAM 024 THRU 048 14 SEER...

Page 16: ...er temperature pulls the liquid into the tank cavity and out of circulation within the system All R 22 likes a nice cool place to rest The net effect is that in cooling mode the system is using the wh...

Reviews: