background image

035-15713-003 REV. A (0500)

14

Unitary Products Group

DEMAND DEFROST:

The defrost control is a demand defrost control. See Figure
13. Due to the arrangement of the refrigerant circuit within the
outdoor coil of these units, frost may accumulate unevenly in
different sections of the coil. However, a normal defrost may
occur even though the coil is not completely covered with
frost. The defrost cycle will start only under the following con-
ditions:
1.

Contactor is energized.

2.

A minimum of 39 minutes have elapsed since the last 
defrost.

3.

The liquid temperature measured by defrost coil sensor 
must be less than 40° F.

4.

The liquid temperature measured by the defrost coil sen-
sor must be below the defrost initiation temperature for 
4.5 minutes continuously.

The defrost mode is identical to the cooling mode except that
the outdoor fan motor stops and the first stage of heat is
turned on through “66" to continue warming the conditioned
space.
The defrost cycle will terminate when the defrost coil sensor
reaches 75° F or after 14 minutes defrost time.

NOTE:  

Under certain low ambient conditions normal initia-

tion of a normal defrost cycle may not occur. There-
fore as a precautionary measure a forced “defrost”
is initiated every six hours to ensure compressor
longevity by returning oil back to the sump of the
compressor.

TEST PINS ON DEMAND DEFROST:

The test pins labeled "speed-up" and "defrost" are provided
to aid in field servicing of the heat pump. See Figure 14. The
pins are designed to be temporarily shorted together either
by a screwdriver or with a 1/4" female spade connector.
When the "speed-up" pins are shorted together. ALL timings
are speeded up by a factor of 64. This reduces the anti-recy-
cle compressor timer from 5 minutes to about 5 seconds and
the defrost terminate time from 14 minutes to 13 seconds:
additionally, the 39 minute minimum run time would be
shorted to about 40 seconds or less if the system has oper-
ated for some period of time since last defrost.
When the "defrost" pins are shorted together, the control will
allow the unit to go into a defrost cycle if the compressor is
operating. When the short is removed, the heat pump will
remain in defrost until the coil temperature reaches 75° F or
14 minutes expires.
If the liquid (coil) temperature happens to be above 75° F, the
short must be maintained to keep the unit in a defrost cycle. It
should be used since the unit WILL REMAIN in defrost until
the short is removed regardless of coil temperature. This
could cause a lockout due to high discharge pressure!

NOTE:  

Anytime the “defrost” shorting pins are jumpered, it

automatically resets all timing cycles. After a power
failure, all timing cycles would also reset except one
that is the 5 minute delay for compressor restart. It
can be reduced, however by jumpering the “speed-
up” pins on the control board.

 FIGURE 17 : 

FLOW DIAGRAM - 018 THRU 048 (10 & 12 SEER)

Summary of Contents for 10 Seer

Page 1: ...TATS 4 INDOOR UNITS 4 REFRIGERANT LINE SWEAT FIT 4 INSULATION OF VAPOR LINE 5 RE ASSEMBLING BRAZING AND CLEANING OF JOINT CONNECTIONS 5 REFRIGERANT LINE SUPPORT 5 CHARGING AND LEAK TESTING 5 TOTAL LIN...

Page 2: ...nd in accordance with the recommendations made by the National Board of Fire Underwriters Limitations for the indoor unit coil and appropriate accesso ries must also be observed The outdoor unit must...

Page 3: ...rom the coil can reduce capacity loss due to wind chill effect Provide ample clearance from shrubs to allow adequate air to pass across the outdoor coil without leaves or branches being pulled into th...

Page 4: ...y important when setting up a refrigeration system and need to be followed completely to insure that a strong flexible and leak tight system is obtained The installation of the copper refrigerant tubi...

Page 5: ...r sags occur We recommend four feet between supports If refrigerant lines are to be attached to the home structure care should be taken to eliminate the transmission of vibra tions Attach the refriger...

Page 6: ...t leaks Replace valve cap finger tight then tighten an additional 1 6 of a turn with a wrench using a back up wrench on the valve body OIL TRAPPING When the outdoor unit is above the indoor coil oil t...

Page 7: ...data sheet Do not use any line sets other than those shown 2 Copper tubing will work harden a The pre charged tubing should be handled carefully b Do not bend or work the tubing any more than nec essa...

Page 8: ...oil b Remove plugs and caps from connections c Check that the rubber seals in connection ends are intact d Be sure surfaces are clean e Lubricate the rubber seals with clean refrigerant oil and make c...

Page 9: ...must include a disconnect switch located within sight of the outdoor unit 2 Use the correct size fuse or circuit breaker as listed on the unit rating plate and data sheet If using nonmetallic sheathe...

Page 10: ...he low voltage junction box See Figures 10 11 12 2 Using wire nuts connect the low voltage wiring within the low voltage box 3 A minimum of 19 AWG wire must be used in connecting the low voltage contr...

Page 11: ...035 15713 003 REV A 0500 Unitary Products Group 11 FIGURE 13 DEMAND DEFROST BOARD 14 SEER FIGURE 14 TIME TEMPERATURE DEFROST BOARD 10 12 SEER...

Page 12: ...035 15713 003 REV A 0500 12 Unitary Products Group FIGURE 15 TYPICAL RESIDENTIAL AIR HANDLER FIGURE 16 TYPICAL MANUFACTURED HOUSING INSTALLATION...

Page 13: ...power to the transformer for at least two seconds TIME TEMPERATURE DEFROST The defrost control is a time temp control which includes a field selectable white tap located at board edge time period bet...

Page 14: ...AND DEFROST The test pins labeled speed up and defrost are provided to aid in field servicing of the heat pump See Figure 14 The pins are designed to be temporarily shorted together either by a screwd...

Page 15: ...035 15713 003 REV A 0500 Unitary Products Group 15 FIGURE 18 FLOW DIAGRAM 060 10 SEER FIGURE 19 FLOW DIAGRAM 024 THRU 048 14 SEER...

Page 16: ...er temperature pulls the liquid into the tank cavity and out of circulation within the system All R 22 likes a nice cool place to rest The net effect is that in cooling mode the system is using the wh...

Reviews: