CAUTION:  READ ALL SAFETY GUIDES BEFORE YOU

START TO INSTALL YOUR UNIT.

SAVE THIS MANUAL

OUTDOOR SPLIT-SYSTEM

HEAT PUMP 

MODELS:  10, 12 AND 14 SEER

1.5 TO 5 TONS

035-15713-003 REV. A (0500)

INSTALLATION 
INSTRUCTION

TABLE OF CONTENTS

GENERAL INFORMATION   . . . . . . . . . . . . . . . . . . .  2
INSPECTION  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  2
REFERENCE  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  2
LIMITATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  2

INSTALLATION  . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

OUTDOOR UNIT  . . . . . . . . . . . . . . . . . . . . . . . . . . .  4
DISCHARGE LINE FILTER-DRIER  . . . . . . . . . . . . .  4
OUTDOOR THERMOSTATS . . . . . . . . . . . . . . . . . .  4
INDOOR UNITS  . . . . . . . . . . . . . . . . . . . . . . . . . . . .  4
REFRIGERANT LINE (SWEAT FIT)   . . . . . . . . . . . .  4
INSULATION OF VAPOR LINE  . . . . . . . . . . . . . . . .  5
RE-ASSEMBLING, BRAZING AND 
CLEANING OF JOINT CONNECTIONS   . . . . . . . . .  5
REFRIGERANT LINE SUPPORT   . . . . . . . . . . . . . .  5
CHARGING AND LEAK TESTING . . . . . . . . . . . . . .  5
TOTAL LINE LENGTH  . . . . . . . . . . . . . . . . . . . . . . .  5
ORIFICE SELECTION (ON SWEAT FIT COILS) . . .  6
REFRIGERANT VALVE OPERATION 
(ON SWEAT FIT UNITS)  . . . . . . . . . . . . . . . . . . . . .  6
OIL TRAPPING   . . . . . . . . . . . . . . . . . . . . . . . . . . . .  6
REFRIGERANT LINES 
(QUICK CONNECT UNITS)  . . . . . . . . . . . . . . . . . . .  7

SEQUENCE OF OPERATION  . . . . . . . . . . . . . . . 12

COOLING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  12
HEATING  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  12
EMERGENCY HEAT  . . . . . . . . . . . . . . . . . . . . . . .  12
10 & 12 SEER WITH TIME/TEMP. DEFROST   . . .  12
14 SEER WITH DEMAND DEFROST  . . . . . . . . . .  12
INSTALLER  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  15
COMPENSATOR TANK FUNCTION  . . . . . . . . . . .  15
OPTIONAL OUTDOOR THERMOSTAT   . . . . . . . .  15

Summary of Contents for 10 Seer

Page 1: ...TATS 4 INDOOR UNITS 4 REFRIGERANT LINE SWEAT FIT 4 INSULATION OF VAPOR LINE 5 RE ASSEMBLING BRAZING AND CLEANING OF JOINT CONNECTIONS 5 REFRIGERANT LINE SUPPORT 5 CHARGING AND LEAK TESTING 5 TOTAL LIN...

Page 2: ...nd in accordance with the recommendations made by the National Board of Fire Underwriters Limitations for the indoor unit coil and appropriate accesso ries must also be observed The outdoor unit must...

Page 3: ...rom the coil can reduce capacity loss due to wind chill effect Provide ample clearance from shrubs to allow adequate air to pass across the outdoor coil without leaves or branches being pulled into th...

Page 4: ...y important when setting up a refrigeration system and need to be followed completely to insure that a strong flexible and leak tight system is obtained The installation of the copper refrigerant tubi...

Page 5: ...r sags occur We recommend four feet between supports If refrigerant lines are to be attached to the home structure care should be taken to eliminate the transmission of vibra tions Attach the refriger...

Page 6: ...t leaks Replace valve cap finger tight then tighten an additional 1 6 of a turn with a wrench using a back up wrench on the valve body OIL TRAPPING When the outdoor unit is above the indoor coil oil t...

Page 7: ...data sheet Do not use any line sets other than those shown 2 Copper tubing will work harden a The pre charged tubing should be handled carefully b Do not bend or work the tubing any more than nec essa...

Page 8: ...oil b Remove plugs and caps from connections c Check that the rubber seals in connection ends are intact d Be sure surfaces are clean e Lubricate the rubber seals with clean refrigerant oil and make c...

Page 9: ...must include a disconnect switch located within sight of the outdoor unit 2 Use the correct size fuse or circuit breaker as listed on the unit rating plate and data sheet If using nonmetallic sheathe...

Page 10: ...he low voltage junction box See Figures 10 11 12 2 Using wire nuts connect the low voltage wiring within the low voltage box 3 A minimum of 19 AWG wire must be used in connecting the low voltage contr...

Page 11: ...035 15713 003 REV A 0500 Unitary Products Group 11 FIGURE 13 DEMAND DEFROST BOARD 14 SEER FIGURE 14 TIME TEMPERATURE DEFROST BOARD 10 12 SEER...

Page 12: ...035 15713 003 REV A 0500 12 Unitary Products Group FIGURE 15 TYPICAL RESIDENTIAL AIR HANDLER FIGURE 16 TYPICAL MANUFACTURED HOUSING INSTALLATION...

Page 13: ...power to the transformer for at least two seconds TIME TEMPERATURE DEFROST The defrost control is a time temp control which includes a field selectable white tap located at board edge time period bet...

Page 14: ...AND DEFROST The test pins labeled speed up and defrost are provided to aid in field servicing of the heat pump See Figure 14 The pins are designed to be temporarily shorted together either by a screwd...

Page 15: ...035 15713 003 REV A 0500 Unitary Products Group 15 FIGURE 18 FLOW DIAGRAM 060 10 SEER FIGURE 19 FLOW DIAGRAM 024 THRU 048 14 SEER...

Page 16: ...er temperature pulls the liquid into the tank cavity and out of circulation within the system All R 22 likes a nice cool place to rest The net effect is that in cooling mode the system is using the wh...