Display Parameter Action/Setting
Description
display
channel C on the small display
Lit Hi
Max on little
display
Assign digital input to display max of
channel A on the small display
Lit HL
Max/min little
display
Assign digital input to toggle max/min of
channel A on the small display
LitHLC
Max/Min little
display
Assign digital input to toggle max/min of
channel C on the small display
Lit LC
Min on little
display
Assign digital input to display min of
channel C on the small display
Lit Lo
Min on little
display
Assign digital input to display min of
channel A on the small display
Little
Little display
Press Enter to assign the small display
parameter (default: Ch-B)
locd
Locked
Enter password to unlock meter
Lt-CLr
Latching-
cleared
Set relay for latching operation with manual
reset only after alarm condition has cleared
mA
4-20 mA
Set meter for 4-20 mA input
mAn
Manual
Press Enter to manually control relays or
analog output operation
math
Math
Select channel C math function
mAx
Maximum
Program maximum mA output allowed
mbus
Modbus
Select to display Modbus input or to assign
Modbus input as the analog output source
menu
Menu button
Assign digital input to Menu button
min
Minimum
Program minimum mA output allowed
No PtS
Num of points
Set meter for 2 to 32-point linearization
O Hold
Relays output
hold
Assign digital input or function keys to hold
all relay states
OFF
Off
Disable relay and front panel status LED,
turn relays off, program off time delay
OFF 1
Off 1
Set relay 1 Off time delay (1-8)
on
On
Enable fail-safe operation, turn relays on,
program on time delay
O-rang
Overrange
Program mA output for display overrange
Out 1
Output 1
Program output 1 value (e.g. 4.000 mA)
Out 2
Output 2
Program output 2 value (e.g. 20.000 mA)
pass
Password
Enter the
Password
menu
Pass 1
Password 1
Set or enter Password 1 (Allows use of the
F1–F3 function keys)
Pass 2
Password 2
Set or enter Password 2 (Allows use of the
F1–F3 function keys and changing the
set/reset points)
Pass 3
Password 3
Set or enter Password 3 (Restricts all
programming & F1–F3 keys)
prog
Program
Enter the
Program
menu
Summary of Contents for YPP6060
Page 73: ...Model YPP6060 Dual Input Process Meter Instruction Manual 73 ...
Page 100: ...Model YPP6060 Dual Input Process Meter Instruction Manual 100 NOTES ...
Page 102: ...Model YPP6060 Dual Input Process Meter Instruction Manual 102 ...
Page 103: ...Model YPP6060 Dual Input Process Meter Instruction Manual 103 NOTES ...