Model YPP6060 Dual-Input Process Meter
Instruction Manual
8
SPECIFICATIONS
Except where noted all specifications apply to operation at +25°C.
General
DISPLAY
Main (big) display: 0.60" (15 mm) high, red LEDs
Second (little) display: 0.46" (12 mm) high, red LEDs
6 digits each (-99999 to 999999), with lead zero blanking
DISPLAY
INTENSITY
Eight user selectable intensity levels
DISPLAY
UPDATE RATE
5/second (200 ms)
OVERRANGE
Display flashes
999999
UNDERRANGE
Display flashes
-99999
DISPLAY
ASSIGNMENT
The main (Big) and second (Little) displays may be
assigned to process values for Channels A (Ch-A), B (Ch-
B), or C (Ch-C), toggle between (Ch-A & Ch-B, Ch-A & Ch-
C, Ch-B & Ch-C, and Ch-A, Ch-B, & Ch-C), toggle between
Channel & units, show channel gross value (no tare) or
toggle net (tare) and gross values, show relay set points,
max & min values, or Modbus input. The second display
may also be set to show engineering units or be off, with no
display.
PROGRAMMING
METHODS
Four front panel buttons, digital inputs, PC and
PRO
PLUS
software, Modbus registers, or cloning using Copy function.
NOISE FILTER
Programmable from 2 to 199 (0 will disable filter)
FILTER BYPASS
Programmable from 0.1 to 99.9% of calibrated span
RECALIBRATION
All ranges are calibrated at the factory. Recalibration is
recommended at least every 12 months.
MAX/MIN
DISPLAY
Max/min readings reached by the process are stored until
reset by the user or until power to the meter is turned off.
PASSWORD
Three programmable passwords restrict modification of
programmed settings.
Pass 1: Allows use of function keys and digital inputs
Pass 2: Allows use of function keys, digital inputs and editing set/reset points
Pass 3: Restricts all programming, function keys, and digital inputs.
NON-VOLATILE
MEMORY
All programmed settings are stored in non-volatile memory
for a minimum of ten years if power is lost.
POWER
OPTIONS
85-265 VAC 50/60 Hz, 90-265 VDC, 20 W max
or jumper selectable 12/24 VDC
±
10%, 15 W max
Summary of Contents for YPP6060
Page 73: ...Model YPP6060 Dual Input Process Meter Instruction Manual 73 ...
Page 100: ...Model YPP6060 Dual Input Process Meter Instruction Manual 100 NOTES ...
Page 102: ...Model YPP6060 Dual Input Process Meter Instruction Manual 102 ...
Page 103: ...Model YPP6060 Dual Input Process Meter Instruction Manual 103 NOTES ...