Model YPP6060 Dual-Input Process Meter
Instruction Manual
37
Programming the Meter (
prog
)
It is
very important
to read the following information, before proceeding
to program the meter:
•
The meter is factory calibrated prior to shipment to read in
milliamps and volts depending on the input selection. The
calibration equipment is certified to NIST standards.
•
Use
the
Scale
menu to scale the process input (e.g. 4-20 mA). A
calibrated signal source is not needed to scale the meter.
•
Use
the
Calibrate
menu to apply a signal from a calibrator or a
flowmeter.
The
Program
menu contains the
Scale
and the
Calibrate
menus for
channels A & B.
The process inputs may be calibrated or scaled to any display value
within the range of the meter.
Note:
The
Scale
and
Calibrate
functions are exclusive of each other.
The meter uses the last function programmed. Only one of these
methods can be employed at a time. The
Scale
and
Calibrate
functions
can use up to 32 points (default is 2). The number of points should be
set in the Advanced menu under the Multi-Point Linearization (
Linear
)
menu selection prior to scaling and calibration of the meter, see page
75 for details.
The process inputs may be calibrated or scaled to any display value
within the range of the meter.
Summary of Contents for YPP6060
Page 73: ...Model YPP6060 Dual Input Process Meter Instruction Manual 73 ...
Page 100: ...Model YPP6060 Dual Input Process Meter Instruction Manual 100 NOTES ...
Page 102: ...Model YPP6060 Dual Input Process Meter Instruction Manual 102 ...
Page 103: ...Model YPP6060 Dual Input Process Meter Instruction Manual 103 NOTES ...