Analog Input Computation Parameters
Located in: Main menu =
CMLP
; Submenu =
AIN
Ref.1.1(6)
Ref.1.1(3)
Ref.1.1(6)
Ref.1.1(3)
Ref.1.1(6)
Ref.1.1(3)
Parameter
Symbol
Name of Parameter
Setting Range and Description
Initial Value
User
Setting
Target Item
in CD-ROM
Analog input-1 bias
Used to correct the PV input value beforehand.
When in normal operation, use the PV Input Bias (BS) operation
mode parameter.
-100.0% to 100.0% of PV input range span
0.0% of PV
input range
span
Analog input-1 filter
OFF (0): Disable
1 to 120 sec.
OFF (0)
A.BS1
A.FL1
A.SR1
A.LC1
A.BS3
A.FL3
A.SR3
A.LC3
Analog input-1
square-root
computation
Performs square-root computation for the PV input value.
OFF (0): Do not compute the square root
ON (1): Compute the square root
OFF (0)
Analog input-1 low
signal cutoff
0.0% to 5.0%
The slope equals “1” at levels below the low-signal cutoff point.
1.0%
A.BS2
Although not used in Single-loop Control, it is shown on the display.
A.FL2
Although not used in Single-loop Control, it is shown on the display.
A.SR2
Although not used in Single-loop Control, it is shown on the display.
A.LC2
Although not used in Single-loop Control, it is shown on the display.
Analog input-3 bias
Used to correct the remote input value.
-100.0% to 100.0% of PV input range span
0.0% of PV
input range
span
Analog input-3 filter
OFF (0): Disable
1 to 120 sec.
OFF (0)
Analog input-3
square-root
computation
Performs square-root computation for the remote input value.
OFF (0): Do not compute the square root
ON (1): Compute the square root
OFF (0)
Analog input-3 low
signal cutoff
0.0% to 5.0%
The slope equals “1” at levels below the low-signal cutoff point.
1.0%