Security-related Parameters
Located in: Main menu =
CMLP
; Submenu =
LOCK
Ref.7.1(2)
Ref.7.1(1)
Front panel data setting
(
䉭
,
䉮
) key lock
OFF (0): Unlock
ON (1): Lock
OFF (0)
Front panel A/M key
lock
OFF (0): Unlock
ON (1): Lock
OFF (0)
A/M
▼
/
▲
Operating parameter
main menu [MODE]
lock
OFF (0): Unlock
ON (1): Lock
OFF (0)
Operating parameter
main menu [LP1] lock
OFF (0): Unlock
ON (1): Lock
OFF (0)
LP1
MODE
Although not used in Single-loop Control, it is shown on the display.
Although not used in Single-loop Control, it is shown on the display.
Operating parameter
main menu [PID] lock
OFF (0): Unlock
ON (1): Lock
OFF (0)
PID
LP2
Operating parameter
main menu [PYS1] lock
OFF (0): Unlock
ON (1): Lock
OFF (0)
PYS1
USR
Although not used in Single-loop Control, it is shown on the display.
Password setting
0: Password not set
1 to 30000
0
PWD
PYS2
Parameter
Symbol
Name of Parameter
Setting Range and Description
Initial Value
User
Setting
Target Item
in CD-ROM
●
SELECT Display Parameters
Located in: Main menu =
CONF
; Submenu =
CSEL
Ref.6.1(1)
Parameter
Symbol
Name of Parameter
Setting Range and Description
Initial Value
User
Setting
Target Item
in CD-ROM
SELECT display-1
registration
OFF (0), 201 to 1023
Select the desired parameter from among the operating
and setup parameters, then register the number
(D register No.) accompanying that parameter.
For example, registering “302” for C.S1 allows you
to change alarm-1 setpoint in operating display.
Numbers for registering alarm SP parameter
for operating display:
Alarm-1 setpoint: 302
Alarm-2 setpoint: 303
Alarm-3 setpoint: 304
Alarm-4 setpoint: 305
Above numbers are alarm setpoint parameters for target
setpoint-1 (1.SP).
Set the registration number of the alarm setpoint parameter for
target setpoint 2 (2.SP), to a value obtained by adding 25 to the
registration number of the alarm setpoint parameter for the
parameter 1.SP.
Likewise, set the registration number of the alarm setpoint
parameter for target setpoint 3 (3.SP), to a value obtained by
adding 25 to the registration number of the alarm setpoint
parameter for the parameter 2.SP.
Likewise, the registration number for 4.SP to 8.SP can be obtained.
OFF (0)
SELECT display-2
registration
SELECT display-3
registration
SELECT display-4
registration
SELECT display-5
registration
C.S1
C.S2
C.S3
C.S4
C.S5