<Toc>
<6. Function Block Diagram and Descriptions>
6-9
IM 05D01B02-41E
Operating Parameters
Function
Parameter
Alarm 1 setpoint
n.A1
Alarm 2 setpoint
n.A2
Alarm 3 setpoint
n.A3
LP1
LP1
LP1
n.PID
n.PID
n.PID
Alarm 4 setpoint
n.A4
LP1
n.PID
Main menu
Submenu
Note: Submenu n.PID (n=1 to 8) corresponds to the target setpoint number selected in the target setpoint number selection
(SPNO).
■
Retransmission Output
PV, target setpoint, or control output can be output to retransmission output 1 (OUTPUT3).
Retransmission output 2 (OUTPUT1) can be used when the control output is relay.
Each function can be set by the following parameters.
Setup Parameters
Function
Parameter
Retransmission output 1 type
RET1
Retransmission output 1 scale
RTH1, RTL1
Retransmission output 2 type
RET2
CMLP
CMLP
CMLP
RET
RET
RET
Retransmission output 2 scale
RTH2, RTL2
CMLP
RET
Main menu
Submenu
■
15 V DC Loop Power Supply
The 15 V DC loop power supply (OUTPUT3) uses the same terminal as retransmission
output 1 or 2. The 15 V DC loop power supply can not be used when retransmission output
1 or 2 is used. To use the 15 V DC loop power supply, set “4” in retransmission output 1
type (RET1) or retransmission output 2 type (RET2).
Each function can be set by the following parameters.
Setup Parameters
Function
Parameter
Retransmission output 1 type
RET1
Retransmission output 2 type
RET2
CMLP
CMLP
RET
RET
Main menu
Submenu
1st Edition : May 31,2000-00