<Toc>
<5. Parameters>
5-11
IM 05D01D02-41E
1st Edition : May 31,2000-00
PID control mode
0: Standard PID control (with output bump at SP change)
1: Fixed Point control (without output bump at SP change)
Choose “Fixed Point Control” when controlling pressure or flow rate.
0
Zone PID selection
0: SP selection
1: Zone PID
0
(C.MD)
Ramp-rate time unit
setting
0: hour, 1: minute
Time unit of setpoint ramp-up (UPR) and setpoint
ramp-down (DNR)
1
(TMU)
Protocol selection
0
Baud rate
0: 600, 1: 1200, 2: 2400, 3: 4800, 4: 9600 (bps)
4
Parity 0:
None
1: Even
2: Odd
1
Stop bit
1, 2
1
Data length
7, 8;
Fixed at 7, when the P.SL parameter is set to MODBUS (ASCII).
Fixed at 8, when the P.SL parameter is set to MODBUS (RTU)
or Ladder Communication.
8
0: PC link communication
1: PC link communication (with sum check)
2: Ladder communication
3: Coordinated master station
4: Coordinated slave station
7: MODBUS (ASCII)
8: MODBUS (RTU)
10: Coordinated slave station (loop-1 mode)
11: Coordinated slave station (loop-2 mode)
(P.SL)
(BPS)
(PRI)
(STP)
(DLN)
Parameter
Symbol
Name of Parameter
Setting Range and Description
Initial Value
User Setting
Target Item
in CD-ROM
AUTO (0)
Anti-reset windup
(Excess integration
prevention)
AUTO (0), 50.0 to 200.0%
Used when the control output travels up to 100% or down
to 0% and stays at this point.
The larger SP, the sooner PID computation
(integral computation) stops.
(AR)
(ZON)
Address
1 to 99
However, the maximum number of stations connectable
is 31.
1
Minimum response
time
0 to 10 (
⫻
10 ms)
0
(ADR)
(RP.T)
If this parameter symbol appears, press the SET/ENT key to return to the FUNC menu.
Caution: Do not change the setpoint of the TEST parameter, otherwise the controller will be disabled.
(TEST)
Ref.2.1(2)
Ref.4.1(2)
Ref.4.1(4)
Communication
function
Ref.2.1(4)