<Toc>
<1. Installation>
1-9
IM 05D01D02-41E
1st Edition : May 31,2000-00
•
On/off determination: For non-voltage contact input, contact resistance of 1 k
or less
is determined as “on” and contact resistance of 20 k
or more as “off.”
For transistor open collector input, input voltage of 2 V or less is determined as “on”
and leakage current must not exceed 100
A when “off.”
•
Minimum status detection hold time: About 1 sec.
Contact Outputs
•
Purpose: Alarm output, FAIL output, and others
•
Number of outputs: 3
•
Relay contact rating: 240 V AC/1 A or 30 V DC/1 A (COM terminal is common.)
Display Specifications
•
PV display:
UT350: 4-digit, 7-segment red LED display, character height of 20 mm
UT320: 4-digit, 7-segment red LED display, character height of 12 mm
•
Setpoint display: 4-digit, 7-segment red LED display, character height of 9.3 mm (for
both UT350 and UT320)
•
Status indicating lamps: LEDs
Safety and EMC Standards
•
Safety: Compliant with IEC1010-1: 1990 and EN61010-1: 1992
Approved by CSA1010
CSA1010 installation category (overvoltage category): CATII (IEC1010-1)
Approved by UL508
•
EMC standards: This instrument complies with the following EMC standards (the
instrument continues to operate at a measuring accuracy of within
20% of the range
during tests):
-
EMI (emission), EN61326-1: 1997+Am1: 1998
-
EMS (immunity), EN61326-1: 1997+Am1: 1998
Construction, Installation, and Wiring
•
Construction: Only the front panel is dust-proof and drip-proof (protection class IP55)
For side-by-side close installation the controller loses its dust-proof and drip-proof
protection.
•
Material: ABS resin and polycarbonate
•
Case color: Black
•
Weight: About 1 kg or less
•
Dimensions:
UT350
96 (W)
96 (H)
100 (depth from panel face) mm
UT320
48 (W)
96 (H)
100 (depth from panel face) mm
•
Installation: Panel-mounting type. With top and bottom mounting hardware (1 each)
•
Panel cutout dimensions:
UT350
92
0
+0.8
(W)
92
0
+0.8
(H) mm
UT320
45
0
+0.6
(W)
92
0
+0.8
(H) mm
•
Installation position: Up to 30
upward facing (not designed for facing downward)
•
Wiring: M3.5 screw terminals (for signal wiring and power/ground wiring as well)
Summary of Contents for UT350
Page 2: ...Blank Page...
Page 46: ...Blank Page...
Page 56: ...Blank Page...
Page 82: ...Blank Page...