<2. Initial Settings>
2-11
IM 05D01D02-41E
1st Edition : May 31,2000-00
■
List of Alarm Types
The table below shows the alarm types and alarm actions.
In the table, codes 1 to 10 are not provided with stand-by actions, while codes 11 to 20 are
provided with stand-by actions.
Alarm action
Alarm action
Alarm type code
Alarm type code
Alarm type
“Open/close” shows status of relay contact,
and “lit” and “unlit” shows status of lamp
Contact
closes
if alarm
occurs
Contact
opens
if alarm
occurs
Contact
closes
if alarm
occurs
Contact
opens
if alarm
occurs
Alarm type
No alarm
OFF
PV high limit
PV low limit
Alarm setpoint
Closed (lit)
Hysteresis
PV
Open (unlit)
1
11
De-energized
on deviation low
limit alarm
Deviation
setpoint
Target SP
Open (lit)
Hysteresis
PV
Closed
(unlit)
6
16
Closed (lit)
Open (unlit)
Open (unlit)
Closed (lit)
Closed (lit)
Open (unlit)
Open (unlit)
Closed (lit)
Closed (lit)
Hysteresis
Open (unlit)
Alarm setpoint
PV
2
12
Deviation high
and low limits
Target SP
PV
Hysteresis
Hysteresis
Deviation setpoint
Closed
(lit)
Open
(unlit)
Closed
(lit)
7
17
Deviation high
limit
Hysteresis
PV
Open (unlit)
Target SP
Deviation setpoint
Closed (lit)
3
13
Deviation within
high and low
limits
Deviation setpoint
Target SP
PV
Hysteresis
Hysteresis
Open
(unlit)
Open
(unlit)
Closed
(lit)
8
18
Deviation low
limit
PV
Target SP
Deviation setpoint
Open (unlit)
Hysteresis
Closed (lit)
4
14
De-energized
on PV high limit
De-energized
on PV low limit
PV
Open (lit)
Alarm setpoint
Hysteresis
Closed
(unlit)
9
19
De-energized on
deviation high
limit alarm
PV
Open (lit)
Target SP
Deviation
setpoint
Hysteresis
Closed
(unlit)
5
15
Alarm setpoint
Hysteresis
PV
Open (lit)
Closed
(unlit)
10
20
SP high
limit
SP low
limit
Alarm setpoint
Hysteresis
SP
Output high
limit
Alarm setpoint
Output value
Hysteresis
Hysteresis
Alarm setpoint
SP
Output low
limit
Hysteresis
Alarm setpoint
Output value
“Open/close” shows status of relay contact,
and “lit” and “unlit” shows status of lamp
Heater
burnout alarm 2
Heater
burnout alarm 1
Sensor grounding
alarm
Sensor grounding alarm
FAIL output
(Note 2)
The controller stops when in a FAIL state.
The control output is set to “OFF” or “0%”
and alarm output is set to “OFF”.
Fault diagnosis
output (Note 1)
Fault diagnosis output
Heater burnout alarms 1 and 2
28
29
30
31
24
25
21
22
23
Note 1: The fault diagnosis output turns on in case of input burnout, A/D converter failure, or reference junction compensation
(RJC) failure.
The control output in case of input burnout or A/D converter failure is set to the value of the PO (Preset Output Value)
setup parameter. In case of RJC failure, the controller continues control under the condition of “RJC = OFF”.
Note 2: The FAIL output is on during normal operation and turns off in case of failure.