1-14
<T
oc>
<1. Installation>
IM 05D01D02-41E
1st Edition : May 31,2000-00
■
UT350 Heating/Cooling Type (Model UT350-2
䊐
)
Heating-side control output
1
2
3
NC
NO
COM
Relay contact output
* Time proportional PID relay contact output
is configured at factory before shipment.
* Available if 4, 7 or 10 is set in the OT
(Control Output Type) setup parameter.
Contact rating: 250 V AC, 3 A
30 V DC, 3 A (resistance load)
23
24
25
26
27
SDB(+)
SDA(-)
RDB(+)
RDA(-)
SG
* Wiring can only be carried out
for controllers with communication
functions.
Maximum baud rate: 9600 bps
RS-485 communication
12
13
11
12
13
12
13
A
b
B
+
-
+
-
TC input
RTD input
mV/V input
Installation category (overvoltage category): II (IEC1010-1)
NOTE
12
13
*
When receiving 4-20 mA DC current signals,
set the PV input type to 1-5 V DC (setpoint “41”).
䊏
Receiving 4-20 mA DC Current
Signals with the Controller
250
Ω
4-20mA
-
+
Note: Connecting a 250
Ω
resistor to the terminals is
optional.
Model: X010-250-2 (resistor with M3.5 crimp-on terminal
lugs)
PV input
* Not configured at factory before shipment
See “2. Initial Settings,” for more
information.
Heating-side control output
16
17
Current/voltage
pulse output
4-20 mA DC,
voltage pulse
(12 V)
+
-
* Available if 5, 6, 8, 9, 11
or 12 is set in the OT
(Control Output
Type) setup parameter.
14
15
14
15
+
-
+
-
Retransmission output
4-20 mA DC
14
15
+
-
4-20 mA DC,
voltage pulse (12 V)
15 V DC loop power supply
14.5-18.0VDC
(21 mA DC max.)
Cooling-side control output
8
9
10
L
N
Power supply
Power supply
Allowable range: 100 to 240 V AC (
10%)
(free voltage)
50/60 Hz shared
6
5
4
7
AL1
AL2
AL3
COM
Relay
Alarm output/cooling-side control output
Alarm-1 output
Alarm-2 output
Alarm-3 output
or cooling-side control
output (Note)
Common
Relay contact rating: 240 V AC, 1 A
30 V DC, 1 A (resistance load)
UT
When switching target
setpoints 1 to 4:
DI1
DI2
1.SP 2.SP3.SP 4.SP
OFF
OFF
OFF
ON
ON
ON
OFF
ON
Contact rating: 12 V DC, 10 mA or more
Correspondence between parameter DIS and external contact input functions
When DIS=4
DI1
DI2
COM
Common
When DIS=3
2.SP when DI1=ON
1.SP when DI1=OFF
STOP when DI2=ON
RUN when DI2=OFF
Common
When DIS=2
Hides the LOCK parameter when DI1=ON.
Shows the LOCK parameter when DI1=OFF.
Common
When DIS=1 (Factory-set default)
2.SP when DI1=ON
1.SP when DI1=OFF
AUTO when DI2=ON
MAN when DI2=OFF
Common
When DIS=OFF
No function
No function
Common
DI1
DI2
COM
+5V
+5V
Contact
Transistor contact
* DIS is a setup parameter.
Changing DIS setpoint allows you to change the function of external contact input.
No function
19
18
20
UT
19
18
20
OT=4 (factory-set default)
OT=5
Correspondence between parameter OT and heating-side/cooling-side output types
OT=6
OT=7
OT=8
OT=9
OT=10
OT=11
OT=12
* OT is a setup parameter. You can change the settings of the parameter OT to change the control output type.
See “2. Initial Settings,” for more information.
The control output types, “relay output” and “voltage pulse output” shown in the table above refer to those of time proportional control.
To change the type to a relay output for on-off control, select “Relay Terminals” and change the setpoint of the proportional band to “0.”
Heating side: Relay output
(terminals , and )
Cooling side: Relay output
(terminals and )
1
2
3
Heating side: Voltage pulse output
(terminals and )
Cooling side: Relay output
(terminals and )
16
17
Heating side: Current output
(terminals and )
Cooling side: Relay output
(terminals and )
16
17
14
15
14
15
14
15
14
15
14
15
14
15
Heating side: Relay output
(terminals , and )
Cooling side: Voltage pulse output
(terminals and )
1
2
3
Heating side: Relay output
(terminals , and )
Cooling side: Current output
(terminals and )
1
2
3
Heating side: Voltage pulse output
(terminals and )
Cooling side: Voltage pulse output
(terminals and )
16
17
Heating side: Current output
(terminals and )
Cooling side: Voltage pulse output
(terminals and )
16
17
Heating side: Voltage pulse output
(terminals and )
Cooling side: Current output
(terminals and )
16
17
Heating side: Current output
(terminals and )
Cooling side: Current output
(terminals and )
16
17
4
7
4
7
4
7
Note: The cooling-side control output is selected if 4, 5 or
6 is set in the OT (Control Output Type) setup
parameter. The alarm-3 output is not available.
The controller is factory-set to the cooling-side control
output (time proportional PID relay contact output).
* PV retransmission is configured at factory before shipment.
* If 15 V DC loop power supply is used,
retransmission output cannot be used.
* The retransmission output and 15 V DC
loop power supply are not available if
the cooling-side control output is set to
“current output” and “voltage pulse output.”
29
28
Heater current
detection input
30
CT2
CT1
COM
CT
CT
* This wiring is only possible
for a controller with a heater
burnout alarm.
Note: External Contact Input
If the power is turned on
when the external contact
input is OFF, the mode
(SP.no or A/M) existing
before the power is turned
off will be continued.
(except for RUN/STOP)
1
2
3
4
5
6
7
8
9
10
21
22
23
24
25
26
27
28
29
30
11
12
13
14
15
16
17
18
19
20
CAUTION
Before carrying out wiring, turn off the power
to the controller and check that cables to be
connected are not alive with a tester or the like
because there is a possibility of electric shock.