<8. EXPLOSION-PROTECTED TYPE INSTRUMENTS>
8-18
IM 01R01B30-00E-E 6th edition October 01, 2014 -00
All Rights Reserved. Copyright © 2003, Rota Yokogawa
8.8 Intrinsically safe EAC (Russia, Belarus, Kazakhstan)
certified RAKD (/GS1)
Certificate No.
: RU С-DЕ.ГБО8.В.00317
Explosion proof
: 0Ex ia IIC T6 X
Ambient temperature
: -40°C ... +65 °C
Safety relevant maximum values:
Transmitter
Current output
Transmitter
Pulse output
Limit switch
Standard
/K1 ... /K3
Type 2
Type 3
Ui [V]
30
16
16
16
Ii [mA]
100
20
25
52
Pi [mW]
750
64
64
169
Li [µH]
730
5
150
150
Ci [nF]
2.4
5
150
150
Temperature specification:
Table 8-4
Configuration
Max.
ambient
temperature
Max.
process
temperature
Temperature
class
Indicator "E"
+ limit switch
type 2
65°C
65°C
T6
50°C
80°C
45°C
100°C
T5
38°C
135°C
T4
Indicator "T"
with limit
switch(es)
type 2
65°C
65°C
T6
80°C
80°C
T5
59°C
100°C
100°C
100°C
T4
73°C
135°C
Indicator "T"
with limit
switch(es)
type 3
24°C
65°C
T6
37°C
80°C
T5
34°C
100°C
57°C
80°C
T4
54°C
100°C
48°C
135°C
Summary of Contents for RAKD series