3.4.5
Unit Timeout Settings
This section explains how to set the time for judging data loss when detecting data dropouts.
Path
GX/GP:
MENU
key >
Browse
tab >
Setting
> Setting menu
Wireless input unit settings
>
Comm time out settings
Web application:
Config.
tab >
Wireless input unit settings
>
Unit number
>
Comm time
out settings
Hardware configurator:
Wireless input unit settings
>
Unit number
>
Comm time out
settings
Description
Setup Item
Selectable Range or Options
Default Value
First unit number
GX20-1/GP20-1/GM10-1: 1 to 50
GX20-2/GP20-2/GM10-2: 1 to 96
1
Last unit number
Same as the first unit number
1
First unit number, Last unit number
Select the target unit number.
Only the unit numbers assigned to GX70SMs that the GX/GP/GM has recognized can be
selected.
Setup Item
Selectable Range or Options
Default Value
On/Off
Off/On
On
Comm time out (sec)*
1 to 7200 (s)
600
* You can set this when On/Off is set to
On
.
On/Off
Set this to
On
to set a timeout.
Comm time out (sec)
Set the time for judging data loss.
Use the GX70SM’s scan/send in Modbus master read cycle as a guideline.
Example:
GX70SM scan/send interval = 5 (min)
Modbus master read cycle = 2 min
Comm time out (sec) = 420 (s)