C6-11
IM 34M06H45-01E
7th Edition : Aug.30, 2019-00
C6.3.3 Operation Control in CPU Configuration
How to set up Operation Control using WideField3
To setup Operation Control using WideField3, use the following procedure.
1. Select [Project]
–[Configuration] from the WideField3 menu.
2. Select the Operation Control tab from the Configuration dialog box.
3. On the Operation Control window, select [Run] or [Stop] for [I/O Module Error] and
[Subunit Communication Error] in the [Error-Time Action] group.
Figure C6.6 Operation Control Setup Using WideFied3
How to set up Operation Control using BASIC (F3BP
)
An I/O module error or subunit communications error generates an error in BASIC.
Design your application program to handle such errors.
Note
In the event of cable discontinuity in only one side of the twisted cable, ERR does not
light up.