<8. Setting Parameters>
8-19
IM 01C27C01-01EN
Table 8.4
Diagnostic Results Summary
Diagnostic Status
Contents
Alert
Type
NAMUR
NE107
Category
Diagnostic Status Detail
Description
Faults in electronics
78
F
AMP_EEPROM_FAIL
Amplifier EEPROM failure
AMP_EEP_IRREGULAR
AMP EEPROM version not correct
G_A_COMM_FAIL
G/A failure
FC_DELTA_T_FAIL
C-side delta T circuit failure
FR_DELTA_T_FAIL
R-side delta T circuit failure
WL_AD_FAIL
Battery voltage not detected (AMP failure)
Faults in sensor or actuator
element
77
F
FC_SENSOR_FAIL
C sensor frequency failure
FR_SENSOR_FAIL
R sensor frequency failure
CAP_T_SENSOR_FAIL
Capsule temperature sensor failure
CAP_EEPROM_FAIL
Capsule EEPROM failure
CAP_EEP_IRREGULAR
CAP EEPROM version not correct
FC_UNOSC_FAIL
C sensor oscillation stop failure
FR_UNOSC_FAIL
R sensor oscillation stop failure
Installation, calibration
problem
76
C
DP_TRIM_SPAN_OUTSIDE "Pressure span adjustment variable
outside of range"
DP_TRIM_ZERO_OUTSIDE "Pressure zero adjustment variable
outside of range"
SP_TRIM_SPAN_OUTSIDE "Static pressure span adjustment
variable outside of range"
SP_TRIM_ZERO_OUTSIDE "Static pressure zero adjustment
variable outside of range"
LCD_OUTSIDE_LIMIT
LCD display outside of limits
Out of service
75
C
AI1_OUT_OF_SERVICE
AI1 O/S mode
AI2_OUT_OF_SERVICE
AI2 O/S mode
AI3_OUT_OF_SERVICE
AI3 O/S mode
Outside sensor limits
74
O
DP_OUTSIDE_LIMIT
Pressure outside of range
SP_OUTSIDE_LIMIT
Static pressure outside of range
CAPT_OUTSIDE_LIMIT
Capsule temperature outside of range
AMPT_OUTSIDE_LIMIT
Amplifier temperature outside of range
Environmental conditions
out of device specification.
73
O
DP_OUTSIDE_RANGE
Pressure setting outside of range
SP_OUTSIDE_RANGE
Static pressure setting outside of
range
Power is critical low:
maintenance need short-term. 71
M
CRITICAL_LOWBAT
Detection of an extreme decrease in
the battery voltage
Power is low:
maintenance need mid-term 70
M
WL_LOWBAT_ALM
Detection of a decrease in the battery
voltage
Simulation is active
68
C
AI1_SIMULATION_ACTIVE
AI1 Simulation mode
AI2_SIMULATION_ACTIVE
AI2 Simulation mode
AI3_SIMULATION_ACTIVE
AI3 Simulation mode
Not applicable for the diagnostic regarding AI2 object and static pressure measurement.
NOTE
A critical low battery alarm may be happened even if battery power of device is remaining. When unexpected
alarm is happened, please restart the device by power off/on or Field Wireless Device Restart Tool.
Field Wireless Device Restart Tool is available in "Downloads" tab at following website:
https://www.yokogawa.com/solutions/products-platforms/field-instruments/.