<10. Parameter Summary>
10-5
IM 01C27C01-01EN
Object
ID
Attribute
ID
Label
Description
Default
value
Handling
4.
TRANSDUCER
block
(continued)
11
Special Order ID
Displays the special order number, if applicable.
---
R
12
Unit Sel1
Selects whether to automatically apply the unit to the
word for the parameter for which the unit display is
selected, or apply the characters that are written to
Display Unit1. (Auto, Custom)
Auto
W
13
Display Unit11
When Custom is selected in Unit Sel1, set the display
unit using 6 characters or less.
NULL
W
14
LCD Intermittetnt
Time
Set the time to turn off display on the LCD indicator.
When 0 is set, it is diplayed in continuous mode.
Unit: second
60 seconds
W
15
XD Filter
Set the damping time to Tranceducer value in the AI1
ans AI2 blocks.
Unit: second
When Measurement mode is set to continuous mode,
it is valid.
2 seconds
W
16
Measurement
Rate
Indicates the cycle to publish the measurement value
and status
0
R
5.
AI1 block
1
Process Value
AL1 is a pressure output object.
Indicates the primary analog value (or corresponding
process value) and status used to execute this
function.
Allows updating data by specifying this for the
Concentrator object.
1. Value: output value of Al object
2. Status: Specify output status of Al object.
1. Value = ---
2. Status = ---
W
2
Block Mode
A universal parameter to indicate the block’s operation
status. Each O/S, Auto, and Man can select from.
1. Target : Specify Al object mode.
2. Actual : Indicates current mode of Al object.
3. Permitted : Indicates the mode selected by
Target of Al object.
4. Normal : Indicate normal status mode of Al
object.
1.
Target=Auto
2.
Actual=Auto
3.
Permitted=
Auto
4.
Normal=Auto
W
3
Concentrator OID
Indicates the Concentrator object value that
corresponds to the data update of the PV value.
3
R
4
Scale
Allows specifying the upper or lower limit for the PV
scaling, unit code, etc.
1. EU at 100% : Indicate the upper limit of the PV
value.
2. EU at 0% : Indicate the lower limit of the PV value.
3. Units Index : Indicate the setting unit used for the
PV value.
4. Decimal : Indicate the digit number below the
decimal point displayed in the LCD indicator.
1. EU at 100%
= 100
2. EU at 0%
= 0
3. Units Index
= %
4. Decimal = 2
W
26
Tag Description
A universal parameter to store the comment that
describes the tag
Al1:
Differential
Pressure
W
27
Process Value
Filter Time
Allows adjusting the time constant for filtering the PV
value. Setting unit: Second. This is enabled for the
Continuous mode.
*2
0 second
W
28
Simulate Switch
A simulation function switch for the AI object test
(Disable, Enable)
1 (Disable)
W
29
Transducer Value
When Simulate Switch is set to Disable, this value
is used as the input value for the AI object. Refer to
Figure 10.1.
Disable
R
30
Simulate Value
When Simulate Switch is set to Enable, this value is
used as the input value for the AI object.
The input value can be changed.
---
W
51
Upper Limit
Indicates the upper limit (URL) for the pressure.
---
R