User Manual

WISE-4220 Series

Model on: WISE 4220

Summary of Contents for WISE-4220 Series

Page 1: ...User Manual WISE 4220 Series Model on WISE 4220 ...

Page 2: ...ation Advantech assumes no liability under the terms of this warranty as a consequence of such events Because of Advantech s high quality control standards and rigorous testing most of our customers never need to use our repair service If an Advantech product is defec tive it will be repaired or replaced at no charge during the warranty period For out of warranty repairs you will be billed accordi...

Page 3: ... and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Opera tion of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense Technical Support and Assistance 1 Visit the Advantech ...

Page 4: ... please contact your dealer immediately Please go to Section 1 6 for package list Warning Warnings indicate conditions which if not observed can cause personal injury Caution Cautions are included to help you avoid damaging hardware or losing data e g There is a danger of a new battery exploding if it is incorrectly installed Do not attempt to recharge force open or heat the battery Replace the ba...

Page 5: ... liquid into an opening This may cause fire or electrical shock 13 Never open the equipment For safety reasons the equipment should be opened only by qualified service personnel 14 If one of the following situations arises get the equipment checked by service personnel 15 The power cord or plug is damaged 16 Liquid has penetrated into the equipment 17 The equipment has been exposed to moisture 18 ...

Page 6: ...omply with the limits for a Class B dig ital device pursuant to Part 15 of the FCC Rules These limits are designed to pro vide reasonable protection against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interfer ence to radio communications H...

Page 7: ...ny interference received including interference that may cause undesired operation Le présent appareil est conforme aux CNR d ISED applicables aux appareils radio exempts de licence L exploitation est autorisée aux deux conditions suivantes 1 le dispositif ne doit pas produire de brouillage préjudiciable et 2 ce dispositif doit accepter tout brouillage reçu y compris un brouillage susceptible de p...

Page 8: ...ent This equipment should be installed and operated with minimum distance 20cm between the radiator your body Déclaration d exposition aux radiations Cet équipement est conforme aux limites d exposition aux rayonnements ISED établies pour un environnement non contrôlé Cet équipement doit être installé et utilisé avec un minimum de 20 cm de distance entre la source de rayonnement et votre corps Dip...

Page 9: ... 2 2 Block Diagram 10 Chapter 3 Hardware Installations 11 3 1 Interface Introduction 12 3 2 Mounting 12 3 2 1 DIN Rail Mounting 12 Figure 3 1 DIN Mounting Kit 13 Figure 3 2 DIN Mounting Install 13 Figure 3 3 DIN Mounting Front 14 Figure 3 4 DIN Mounting Back 14 3 2 2 Wall Mounting 15 Figure 3 5 Wall Mounting Kit Dimension 15 Figure 3 6 Wall Mounting Install 1 15 Figure 3 7 Wall Mounting Install 2 ...

Page 10: ... the Module 22 4 2 6 Configuring Cloud Server 39 Appendix A Modbus Mapping Table 43 A 1 Modbus Function Code Introduction 44 A 2 WISE 4220 S231 Modbus Mapping Table 44 Appendix B REST for WISE 4220 Series 47 B 1 Introduction 48 B 2 REST Resources for WISE 4220 Series 48 B 2 1 Sensor Input 48 ...

Page 11: ...Chapter 1 1 Product Overview ...

Page 12: ...ly and Specifications 1 2 Mechanical Design and Dimensions 1 2 1 WISE 4220 Series Dimension Figure 1 1 ME Dimension Front Side Function Model Description Wireless Sensor Node WISE 4220 S231 IoT Wireless Sensor Node with Temperature Humidity Sensors ...

Page 13: ...ee a switch inside The battery socket is no function for WISE 4220 series It is reserved for WISE 4220 series Switch Description Position ON Default OFF SW1 Operation Mode P1 Normal Mode Initial Mode P2 N A N A Note After the position 1 of SW1 been changed users need to power on the module again to apply the operation mode ...

Page 14: ...N 61000 4 8 2010 EN 61000 6 1 2017 EN 61000 6 2 2017 EN 61000 6 3 2007 A1 2011 AC 2012 EN 61000 6 4 2007 A1 2011 EN 301 489 1 V2 1 1 2017 02 EN 301 489 17 V3 1 1 2017 02 LED Color Indication Behavior Status Green Blink 2Hz Wait for connection 0 5Hz Network Connected ON 30 Sec When enable LOCATE function Com Yellow Blink When TX RX data in transmission AP Infra Green ON Limited AP Mode OFF Station ...

Page 15: ...47 CFR FCC Part 15 Subpart C Section 15 247 ANSI C63 10 2013 IC 9404A WISE 4220 Canada RSS 247 Issue 2 2017 02 Canada RSS Gen Issue 4 2014 11 ANSI C63 10 2013 NCC LP0002 ANSIC63 10 2013 TELEC 001 A08148 RED Processing EN 300 328 V2 2 2 2016 11 EN 63211 2008 RCM AS NZS 2772 2 2011 AS NZS 4268 2017 SRRC Processing 1 6 Package Information WISE 4220 S231 WISE 4220 module with bundle antenna and termin...

Page 16: ...WISE 4220 Series User Manual 6 ...

Page 17: ...Chapter 2 2 General Specification ...

Page 18: ...g DIN 35 rail wall and stack Dimensions W x H x D 69 x 38 x 102 mm Operation Temperature 25 70 C 13 158 F Storage Temperature 40 85 C 40 185 F Operating Humidity 10 95 RH non condensing Storage Humidity 0 95 RH non condensing Note Equipment will operate below 30 humidity However static electricity problems occur much more frequently at lower humidity levels Make sure you take adequate precautions ...

Page 19: ...n JSON format Supports Web Server in HTML5 with JavaScript CSS3 2 2 WISE 4220 S231 2 2 1 I O Specification 2 2 1 1 Temperature Sensor Input Operating Range 25 C 70 C 4 F 157 9 F Data Resolution 0 1 C F K Accuracy 1 0 C Vertical Installation Update Rate Minimum 1 seconds Response Time 15 seconds Achieving 63 of a step function Long Term Drift 0 05 C Year 0 09 F Year 2 2 1 2 Humidity Sensor Input Op...

Page 20: ...WISE 4220 Series User Manual 10 2 2 2 Pin Assignment Figure 2 1 Pin Assignment 2 2 3 Block Diagram Figure 2 2 Block Diagram ...

Page 21: ...Chapter 3 3 Hardware Installations ...

Page 22: ...lled in the field site under the following methods 3 2 1 DIN Rail Mounting The WISE 4220 module can also be fixed to the cabinet by using mounting rails You need to assemble the DIN rail adapter to WISE 4220 module with flathead screw driver as below When the module is mounted on a rail you may also consider using end brackets at each end of the rail to keep the module from sliding horizontally al...

Page 23: ...13 WISE 4220 Series User Manual Chapter 3 Hardware Installations Figure 3 1 DIN Mounting Kit Figure 3 2 DIN Mounting Install ...

Page 24: ...WISE 4220 Series User Manual 14 Figure 3 3 DIN Mounting Front Figure 3 4 DIN Mounting Back ...

Page 25: ...l Mounting Each WISE 4220 module is packed with a plastic wall mounting bracket Users can refer to the bracket dimensions and assembly steps to configure an optimal place ment in a wall panel or cabinet Figure 3 5 Wall Mounting Kit Dimension Figure 3 6 Wall Mounting Install 1 ...

Page 26: ...WISE 4220 Series User Manual 16 Figure 3 7 Wall Mounting Install 2 ...

Page 27: ...ing ring through the middle hole of it Note that you should unlock the pole mounting ring with a screw driver before putting it through the device Then mount the WISE 4220 module steadily to the pole by locking the pole mounting ring tightly Figure 3 8 Polar Mounting Front Figure 3 9 Polar Mounting Back ...

Page 28: ...DC Screw terminals Vs and Vs are for power supply wiring Figure 3 10 Power Wiring 3 3 2 I O Units The system uses a plug in screw terminal block for the interface between I O mod ules and field devices The following information must be considered when connect ing electrical devices to I O modules The terminal block accepts wires from 0 5 mm to 2 5 mm Always use a continuous length of wire Do not c...

Page 29: ...Chapter 4 4 System Configuration ...

Page 30: ...eloped with public HTML 5 but for detailed indication and data transmission modes the type of web utility will depend on web page of the operating system For mobile devices the minimum system requirements of web browsers are as below Safari 6 in Apple iOS Web Browser in Google Android 4 0 Ice Cream Sandwich Chrome in Google Android 4 0 Ice Cream Sandwich For PC platforms the minimum requirements o...

Page 31: ...0000000 View module status only Not allow to change configurations Functions Account root admin user Device information View View View Device setting Edit Edit Deny System Restart Edit Edit Edit Module Locate Edit Edit Edit Change passwords Edit Deny Deny Reset Password Edit Deny Deny Reset to default Edit Deny Deny Access control configurations Edit Edit Deny Group configurations Edit Edit Deny D...

Page 32: ...on Steps 4 2 5 1 Login Web Configuration Page Mode WISE 4220 Series Initial Mode Fixed IP address 192 168 1 1 Fixed Wi Fi Mode AP Mode Normal Mode Default IP address 192 168 1 1 Default Wi Fi Mode AP Mode Login 1 Connect your smartphone to your local Ethernet network and open the browser of your smartphone 2 Enter IP address of module with con fig for example the default URL is http 192 168 1 1 co...

Page 33: ...rmation In the information page you can see the dashboard module detail network setting and module information including the firmware version Change User 5 Scroll down the tab and you can change the login user here Menu 6 Click the button on the top and you can switch to other pages ...

Page 34: ...here Description Any comments about this module can be stated here Working Mode Refer to 4 2 4 for Operation Mode 4 2 5 4 Wireless Status For WISE 4220 series users can refer to the WLAN RSSI indicators for the signal quality in Wireless Status section It also shows the MAC ID of the client device If the module is in AP Mode the WLAN RSSI Level and Refresh button will not be shown 4 2 5 5 Network ...

Page 35: ...e When setting the module to AP mode users can configure the SSID and also decide how the WISE module works including security The AP Mode IP Set tings are fixed and do not allow users to make changes Infrastructure Mode When using the module in Infrastructure Mode users need to enter the SSID of the Access Point AP that the WISE module is going to connect and config ure the security type here WIS...

Page 36: ... DO and AI You can select the models which meet your requirements based on the applications WISE 4220 S231 Temperature and Humidity Sensors WISE 4220 S231 is equipped with built in temperature and humidity sensors As you can see the IO status section shows measured results Channel 0 and 1 present the measured temperatures and humidity from the sensors respectively ...

Page 37: ... and minimal measured results from the historical record by selecting Max and Min tabs By clicking Reset you can reset the max imal and minimal records in the module You can also change the settings of channel 0 and 1 in the configuration tab The fields that can be changed are shown as follows ...

Page 38: ...ure the Web Server Port Host Idle timeout and decide whether to enable Communication WDT or not in the section The Web Server Port field deter mines which Ethernet port will be used for the web service such as the web configu ration and RESTful Web API The default port is 80 but if you change the port number to 8080 you will have to access the module through http 192 168 1 1 8080 config in AP mode...

Page 39: ...as FSV of output channel and system log Time Date SNTP You can see the current time select the time zone you want to use and calibrate the time by clicking Click Me to inquire time from host devices You can enable SNTP so that the module can act as an SNTP client to perform time synchronization from an assigned SNTP server ...

Page 40: ...us address sections 0X and 4X General Configuration Scan Interval determines the I O polling interval in the I O Status section The changed values will not be saved into the module The change is only valid until the module is powered off The FSV by Communication WDT determines whether to enable the FSV function triggered by communication with WDT You can enable the FSV function for all the output ...

Page 41: ...configuration and click the Download Configuration File button The configurations will be saved as a file Update Configuration File to Module Go to the Firmware page in system configuration and click the icon to select the configuration file you want to upload from the local folder Before uploading the configuration file to the module select whether or not to apply the IP settings to the WISE modu...

Page 42: ...th the firmware version as these have to been updated at the same time Here is the table list the versions in following figure Update Firmware Go to the Firmware page in system configuration and click the icon to select the configuration file you want to upload from the local folder You can find the latest offi cial release firmware file at the Advantech support site http support advan tech com su...

Page 43: ...onditions section in Data Configuration to choose the method that will be used to log data If you check By Period box it will enable peri odic logging and the log period can be assigned in the following field Note that the unit of this field is 0 1 second meaning that the status of I O will be logged every min ute if you enter 600 here If you check the box By Communication WDT once the condition o...

Page 44: ...he status of checked channel periodically After you check Log Enabled box you can check the Deviation Enabled box if you want to log data when the deviation matches the crite ria set in Sensor Deviation Value field of the IO Status section You can also choose to log the events that trigger high and low alarms by checking High Alarm and Low Alarm boxes The By Sensor tab is used to decide what kinds...

Page 45: ...onvert the data from json to csv Before querying the logged data you can configure the format of the file You can determine whether the data comes with a UUID or MAC ID and choose the type of time stamp For the latest version of WISE module which supports Local Date and Time GMT the time stamp will be reported in the format like this 2015 08 27T15 20 29 08 00 whereas the time stamp will look like ...

Page 46: ...WISE 4220 Series User Manual 36 ...

Page 47: ...e to use the example agent provided by WISE you need to confirm the Server IP and Server Port and make sure the server port you configure is not occupied by another application on your private server To setup your own application to retrieve files from WISE you need to configure the URL We also support SSL security with Dropbox in order to provide you a safe private cloud solution Once SSL securit...

Page 48: ...nd start uploading The data will be pushed to the cloud in the format of csv Push Notification For Cloud Logger functions including Dropbox Cloud Logger and other private serv ers data comes from the local memory of WISE You can pack data from the WISE data logger into a file and then push it to the web server Then you can push the lat est data when the log condition is triggered with the events s...

Page 49: ...ab of Configuration 3 Select Dropbox as the cloud server 4 The browser will open a new window for Dropbox Enter your Dropbox account information including E mail and Password then click Sign in Note The following instructions use Dropbox Make sure Dropbox provide their service in your region or find an alternative public cloud service Note Before start to configure cloud sever please make sure WIS...

Page 50: ...loud Logger Apps to access your Dropbox account to store the data log file 6 Dropbox will then provide a code Copy this code and return to the configuration web page of the WISE module 7 Click Next to enter the code 8 Paste the code provided by WISE Cloud Logger then click Submit ...

Page 51: ...hapter 4 System Configuration 9 If your WISE 4220 module is correctly connected to the Internet you will be able to set the functions successfully Click Close to return to Configuration 10 You will then see the Link Status shows Ready ...

Page 52: ...WISE 4220 Series User Manual 42 ...

Page 53: ...Appendix A A Modbus Mapping Table ...

Page 54: ...ON OFF 10 Preset Multiple Registers Write multiple data in 16 bit integer format Address 0X Channel Description Attribute 00101 Temperature Reset Historical Max Sensor Value Write 00102 Humidity Write 00111 Temperature Reset Historical Min Sensor Value Write 00112 Humidity Write 00131 Temperature High Alarm Flag Read 00132 Humidity Read 00141 Temperature Low Alarm Flag Read 00142 Humidity Read 050...

Page 55: ...ensor value sensor not ready 1 31 Reserved Type Code Sensor type Sensor type and unit 4096 0x1000 Temperature Temperature C 4097 0x1001 Temperature F 4098 0x1002 Temperature K 4128 0x1020 Humidity Humidity Bit Order Description 0 Built in logging is out of memory for IO log No space left 1 Built in memory errors 2 Built in logging is out of memory for System log No space left 3 Cloud upload fail 4...

Page 56: ...WISE 4220 Series User Manual 46 ...

Page 57: ...Appendix B B REST for WISE 4220 Series ...

Page 58: ...formation command list can be referenced B 2 REST Resources for WISE 4220 Series B 2 1 Sensor Input sensor_value slot_0 ch_num Description Retrieves information about the sensor input value resource on specific slot URL Structure http 10 0 0 1 sensor_value slot_0 http 10 0 0 1 sensor_value slot_0 ch_num where num 0 the channel number HTTP Method GET Returns the representation of all of analog inpu...

Page 59: ...t 0 EgF 0 000 HEgF 0 000 LEgF 0 000 LoA 0 HiA 0 ClrH 0 ClrL 0 PUT None PATCH Single Multi Channel Request PATCH sensor_value slot_0 Single Channel Request PATCH sensor_value slot_0 ch_num Example Request PATCH sensor_value slot_0 Content type application json SVal Ch 0 ClrH 0 Ch 1 ClrL 0 Response 200 OK Request PATCH sensor_value slot_0 ch_1 Content type application json ClrL 0 Response 200 OK ...

Page 60: ...inimum Sensor value Channel Engineering data floating type EgF Number R Sensor engineering data the value is floating type Unit According sensor type code For example 999 120 999 12 C 3 220 3 22 C Maximum Sensor Engineering data floating type HEgF Number R Sensor max engineering data the value is floating type Unit According sensor type code For example 10 200 10 2 C 5 120 5 12 C Minimum Sensor En...

Page 61: ...anual Appendix B REST for WISE 4220 Series Sensor type code table Type Code Sensor type Sensor type and unit 4096 0x1000 Temperature Temperature C 4097 0x1001 Temperature F 4098 0x1002 Temperature K 4128 0x1020 Humidity Humidity ...

Page 62: ...ations are subject to change without notice No part of this publication may be reproduced in any form or by any means electronic photocopying recording or otherwise without prior written permis sion of the publisher All brand and product names are trademarks or registered trademarks of their respective companies Advantech Co Ltd 2017 ...