IM 12J05C01-01E
x
In each I.S. Fieldbus segment only one active source, normally the FM Approved FISCO
barrier, is allowed to provide the necessary power for the Fieldbus system. All other
equipment connected to the bus cable has to be passive (not providing energy to the
system), except to a leakage current of 50
μ
A for each connected device. Separately
powered equipment needs a galvanic isolation to insure that the I.S. Fieldbus circuit
remains passive.
x
The cable used to interconnect the devices needs to comply with the following
parameters:
Loop resistance R’: 15 … 150
Ω
/km; Inductance per unit length L’: 0,4 … 1 mH/km
Capacitance per unit length C’: 80 … 200 nF/km
(C’ = C’ line/line + 0,5 C’ line/screen if both line are floating)
(C’ = C’ line/line + C’ line/screen if the screen is connected to one line)
Length of spur cable: max. 30 m
Length of trunk cable: max. 1 km
Length of splice : max. 1 m
WARNING
- Substitution of components may impair Intrinsic Safety
- To prevent ignition of flammable or combustible atmospheres, disconnect power
before servicing or read, understand and adhere to the manufacturer’s live
maintenance procedures.
General Specifications 2-16
Application Doc. No.: IKE031-A10 P.7 to P.8
Summary of Contents for DO202G
Page 7: ...IM 12J05C01 01E LT LV PL EST SLO H BG RO M CZ SK...
Page 11: ...IM 12J05C01 01E 1 4 Introduction...
Page 31: ...IM 12J05C01 01E General Specifications 2 20...
Page 37: ...IM 12J05C01 01E...
Page 65: ...IM 12J05C01 01E...
Page 69: ...IM 12J05C01 01E 2 4 Appendix...
Page 74: ...IM 12J05C01 01E Appendix 2 9...
Page 78: ...IM 12J05C01 01E Appendix 2 13...
Page 82: ...IM 12J05C01 01E Appendix 2 17...