IM 12J05C01-01E
2-13 General Specifications
2-11. Control Drawing of DO202S FF/PB Specification (FM Intrinsically safe Entity)
Unclassified Location
Classified Location
Division 1
FM Approved
barrier
Voc (Vt)
d
24 V
Ioc (It)
d
250 mA
Poc (Pt)
d
1.2 W
Ca
t
220pF+ Ccable
La
t
0 H + Lcable
Sensor
Connections
Max. cablelength: 60 mtr.
Cable dia. : 3…12 mm.
FM Class I, DIV. 1, Group ABCD
T4 for ambient temp.
d
55
q
C
-
+
I.S.
certified
Terminator
I.S.
certified
Terminator
DO202S-F
or DO202S-P
Transmitter
Transmitter
-
+
Sensor
Connections
-
+
-
+
x
Sensor(s) are of a passive type to be regarded as 'simple apparatus', devices which
neither store nor generate voltages over 1.5 V, currents over 0.1 A, power over 25 mW or
energy over 20
P
J, or are FM Approvals entity approved and meet connection
requirements.
x
Electrical data of the DO202S-F & DO202S-P:
-
Supply
circuit:
Maximum input voltage Vmax = 24 V
Maximum input current Imax = 250 mA
Maximum input power Pi = 1.2 W
Effective internal capacitance Ci = 220 pF;
Effective internal inductance Li = 0
P
H.
-
Sensor input circuit:
Maximum output voltage Vt = 14.4 V; Maximum output current It = 10 mA
Maximum allowed external capacitance Ca = 643 nF
Maximum allowed external inductance La = 340 mH
x
Any FM Approved barrier may be used that meets the following requirements:
Voc or Vt
d
24 V
Ioc or It
d
250 mA
Poc or Pt
d
1.2 W
Ca
t
220 pF + Ccable; La
t
0
μ
H + Lcable
When installing this equipment, follow the manufacturer’s installation drawing.
Installation should be in accordance with ANSI/ISA RP 12.06.01 “Installation of
Intrinsically Safe Systems for Hazardous (Classified) Locations” and the National
Electrical Code (ANSI/NFPA 70).
Associated apparatus connected to the barrier must not use or generate more than
250 Vrms or Vdc.
x
Resistance between Intrinsically Safe Ground and earth ground must be less than 1.0
Ohm.
x
In case of using cable glands in Outdoor location, they shall be UV rated or made of metal.
WARNING
- Substitution of components may impair Intrinsic Safety
- To prevent ignition of flammable or combustible atmospheres, disconnect power
before servicing or read, understand and adhere to the manufacturer’s live
maintenance procedures.
Summary of Contents for DO202G
Page 7: ...IM 12J05C01 01E LT LV PL EST SLO H BG RO M CZ SK...
Page 11: ...IM 12J05C01 01E 1 4 Introduction...
Page 31: ...IM 12J05C01 01E General Specifications 2 20...
Page 37: ...IM 12J05C01 01E...
Page 65: ...IM 12J05C01 01E...
Page 69: ...IM 12J05C01 01E 2 4 Appendix...
Page 74: ...IM 12J05C01 01E Appendix 2 9...
Page 78: ...IM 12J05C01 01E Appendix 2 13...
Page 82: ...IM 12J05C01 01E Appendix 2 17...