![YOKOGAWA Centum VP Technical Information Download Page 91](http://html1.mh-extra.com/html/yokogawa/centum-vp/centum-vp_technical-information_3456521091.webp)
Appendix 1 CSA NI/FM NI/IECEx Ex “ec”/ECAS-EX Ex “ec”
App.1-15
TI 33Q01J30-01E
Yokogawa Electric Corporation
Model
CENTUM VP FIO
Title
Control drawing
No.
NFM020-A13
Page
14
Revision
70
Nonincendive Field Wiring Parameter (Equipment receiving energy) (Continued) (*1)
Model
Vmax
(V)
Imax
(mA)
Ci
(μF)
Li
(μH)
Remark
ADV151
Redundant
30
11
0.001
10
Voltage input mode
Single
30
5.5
0.001
10
ADV551
Redundant
26.4
100
0.28
10
ON/OFF status output mode,
Without surge absorber
Single
26.4
100
0.14
10
ON/OFF status output mode
ADV161
Redundant
30
6.7
0.001
10
Voltage input mode
Single
30
3.4
0.001
10
ADV561
Redundant
26.4
100
0.275
0
ON/OFF status output mode
Single
26.4
100
0.138
0
ALR111
Redundant
—
—
—
—
(*2)
Single
—
—
—
—
ALR121
Redundant
—
—
—
—
(*2)
Single
—
—
—
—
ALE111
Redundant
—
—
—
—
(*2)
Single
—
—
—
—
ALF111
Redundant
—
—
—
—
(*2)
Single
—
—
—
—
AEP7D
TM1, M2
—
—
—
—
(*2)
AEPV7D
TM1, TM2
—
—
—
—
(*2)
AEP9D
TM1, M2
—
—
—
—
(*2)
A1BD5D
TM3
—
—
—
—
Ready input(*2)
60
20
0
0
Ready input DC
*1 These parameters are applied to all modes of each model if the mode is not otherwise remarked.
*2 Wiring for Division 2 (such as conduit systems) must comply with NEC or Local Electrical Code
of each country.
Dec. 3, 2021-00