4. Intrinsic Safety Explosion Protection Instrumentation
4-2
TI 33Q01J30-01E
4.1
Intrinsic Safety Explosion Protection
Instrumentation Using Barrier base plates
I.S. barriers comply with the I.S. explosion protection standard and can be mounted on the base
plate (A2BN4D) (*1) which are connected to the I.S. equipment installed in the hazardous area
with explosion-proof wiring. As for the intrinsic safety explosion protection instrumentation, refer
to the instruction manual of the I.S. barriers of MTL products.
*1:
Refer to “Base Plates (for N-IO)” (GS 33J62F40-01EN) for more details.
4.1.1
Intrinsic Safety Explosion Protection of ATEX/UKEX
Standard
A2BN5D base plate for barrier
A2BN5D base plate for barrier can be connected to the I.S. equipment installed in the hazardous
area with explosion-proof wiring and can be installed in Zone 2 by mounting in a keyed metal
cabinet with protection rating of IP54 or higher as shown in the following figures. Please refer to
the instruction manual of P+F I.S. barriers for installation of I.S. barriers.
Explosion-proof Specifications and Complied Standard
[Explosion-proof specifications]
II 3(1) G Ex ec [ia Ga] IIC T4 Gc
II (1) D [Ex ia Da] III C
I (M1) [Ex ia Ma] I
[Complied standard]
EN IEC 60079-0:2018
EN 60079-11:2012
EN IEC 60079-7:2015 + A1:2018
Note: Regarding the latest conformity standard, refer to the GS 33J01A10-01EN “Integrated Production Control System CENTUM VP
System Overview”.
Wiring of Intrinsic Safety Explosion Protection
An intrinsic safety circuit must be isolated from non-intrinsic safety circuit. Wiring should be
prepared in accordance with EN 60079-14, or the standard of the country and the area in which it
is set. In regards to the further wiring than the base plate for barrier (A2BN5D), take notice that it
should be an intrinsic safety circuit. The wiring in cabinet should keep the distance to non-intrinsic
safety circuit.
After setting, check the wiring according to the checklist described in EN 60079-17.
Parameter of Intrinsic Safety
Please refer to the P+F’s instruction manual of I.S. barriers installed in the base plate for barrier
(A2BN5D) for the parameter of Intrinsic Safety.
Nov. 10, 2022-00