3. Explosion Protection Instrumentation in Zone 2/Division 2
3-24
TI 33Q01J30-01E
3.2
Ex “ec”, Type “n”
Ex “ec”/Type “n” is a construction that enhances safety not to cause a spark, an arc or high
surface temperatures in a normal operation and also to avoid causing a spark, an arc or high
surface temperatures under defined conditions such as an overload.
A Field Control Unit (for Vnet/IP), a node unit for FIO/N-IO and an I/O module of CENTUM have
acquired ATEX Ex “ec” or ATEX Type “n”. Also, a Field Control Unit (for Vnet/IP), a node unit
for FIO/N-IO and an I/O module of CENTUM have acquired UKEX Ex “ec” or UKEX Type “n”.
And a Field Control Unit (for Vnet/IP), a node unit for FIO/N-IO, and a communication module of
CENTUM have acquired IECEx Ex “ec” or IECEx Type “n”.
An N-IO field enclosure has acquired ATEX Ex “ec”, IECEx Ex “ec”, and UKEX Ex “ec”.
This approval permits that the products above can be used in hazardous areas such as Zone 2.
3.2.1
ATEX Ex “ec”, ATEX Type “n”
E
xplosion-proof specifications, Complied standard, and Compliant
Products
The references are listed in the following table.
Explosion
protection
construction
Reference of Explosion-proof specifications, Complied Standard, and Compliant
Products
FIO System
N-IO System
FCU
FIO Node
Unit
FCU
N-IO Node
Unit
FIO Node
Unit
N-IO field
enclosure
A2BN4D A2BN5D
ATEX Ex “ec” (*1)
App. 2.1
App. 2.1
App. 2.2
App. 2.2
App. 2.1
App. 2.3
–
App. 2.5
ATEX Type “n”
–
–
–
–
–
–
App. 2.4
–
–: Non-compliant
Note: Regarding the latest conformity standard, refer to the GS 33J01A10-01EN “Integrated Production Control System CENTUM VP
System Overview”.
*1:
The following products that use sealed devices also comply with ATEX Type “nC”.
AFV30S, AFV30D, ANB10S, ANB10D, ANB11S, ANB11D, A1BD5D, A2FV50S, A2FV50D, A2ZN3D, A2BE1D, A2FU2,
A2ZN70D, and A2ZN60D.
3.2.2
IECEx Ex “ec” , IECEx Type “n”
E
xplosion-proof specifications, Complied standard, and Compliant
Products
The references are listed in the following table.
Explosion
protection
construction
Reference of Explosion-proof specifications, Complied Standard, and Compliant
Products
FIO System
N-IO System
FCU
FIO Node
Unit
FCU
N-IO Node
Unit
FIO Node
Unit
N-IO field
enclosure
A2BN4D A2BN5D
IECEx Ex “ec”
(*1)
–
–
App. 1.3
App. 1.3
App. 1.3
App. 1.4
–
App. 3.2
IECEx Type “n”
–
–
–
–
–
–
App. 3.1
–
–: Non-compliant
Note: Regarding the latest conformity standard, refer to the GS 33J01A10-01EN “Integrated Production Control System CENTUM VP
System Overview”.
*1:
The following products that use sealed devices also comply with IECEx Type “nC”.
A2FV50S, A2FV50D, A2BE1D (Applied VP6F1800), A2FU2, A2SDV506, A2NN70D, and A2NN60D.