![YOKOGAWA Centum VP Technical Information Download Page 78](http://html1.mh-extra.com/html/yokogawa/centum-vp/centum-vp_technical-information_3456521078.webp)
Appendix 1 CSA NI/FM NI/IECEx Ex “ec”/ECAS-EX Ex “ec”
App.1-2
TI 33Q01J30-01E
Yokogawa Electric Corporation
Model
CENTUM VP FIO
Title
Control drawing
No.
NFM020-A13
Page
1
Revision
70
Date
2021-04-28
Revised pages
1−6, 11−15
■
Applicable standards:
FM 3600:2018
FM 3611:2018
FM 3810:2018 (Note 1)
ANSI/UL 121201 Ed. 9 (2019)
ANSI/UL 61010-1 Ed. 3 (2012) (Note 1)
ANSI/UL 61010-2-30 Ed. 1 (2012) (Note 1)
ANSI/UL 61010-2-201 Ed. 1 (2014) (Note 1)
Note 1: Instead of the listed standards, FM 3810: 2005 and ANSI/ISA-61010-1-2004 apply to the
following models.
ACCC01, YCB138
AKB131, AKB132, AKB133, AKB134, AKB135, AKB136, AKB161, AKB162
The models which conform to these standards are listed in the following tables of the ambient
temperature ranges.
■
Markings:
CL I DIV 2 GP ABCD T4
■
Specific Conditions of Use:
- The equipment shall be installed in a lockable metal cabinet. The suitability of the installation shall
be determined by the authority having jurisdiction.
- The ambient temperature ranges are as follows.
Classifications
Model
Ambient Temperature (*1)
Field control unit
AFV30S-S
□
1
□
E
□
AFV30S-S
□
1
□
F
□
0 to 50
°
C
AFV30D-S41
□
E
□
AFV30D-S41
□
F
□
AFV30S-A
□
1
□
E
□
AFV30S-A
□
1
□
F
□
AFV30D-A41
□
E
□
AFV30D-A41
□
F
□
Node unit
ANB10S-
□□
E
ANB10S-
□□
G
0 to 60
°
C
ANB10S-
□□
F
−20 to 70
°
C
ANB10D-4
□
E
ANB10D-4
□
G
0 to 60
°
C
ANB10D-4
□
F
−20 to 70
°
C
ANB11S-
□□
E
0 to 60
°
C
ANB11S-
□□
F
−20 to 70
°
C
ANB11D-
□□
E
0 to 60
°
C
ANB11D-
□□
F
−20 to 70
°
C
Base Plate
A2BE1D-S1
□
0
0 to 50 °C
A2BE2D-S100
0 to 60
°
C
A2BE2D-S130
−20 to 70
°
C
Interface unit for FCU A2FU2-
□
1
□
0
0 to 50 °C
Dec. 3, 2021-00