![YOKOGAWA Centum VP Technical Information Download Page 48](http://html1.mh-extra.com/html/yokogawa/centum-vp/centum-vp_technical-information_3456521048.webp)
3. Explosion Protection Instrumentation in Zone 2/Division 2
3-19
TI 33Q01J30-01E
Instruction on Voltage Input Mode Wiring
The total current value of the channels must be within the rated current (limit) for DC power
supply.
But if the total current value exceeds the rated current, reduce the number of channels to be
supplied at on time, and prepare the same DC power supply for each channel group.
In such a case, the polarity of power sources should be the same.
Mount ADV151, ADV161, AED5D, A1BD5D, AKB331 and AKB337 in the same cabinet.
When ADV151 or ADV161 is mounted in a cabinet different from that for AED5D or A1BD5D,
apply explosion-proof wiring defined in each country for AKB331 or AKB337.
ADV151/ADV161
Fuse
LED
AED5D
1A
1B
2A
2B
3A
3B
16A
16B
SA
SB
+
–
IN1
IN2
IN3
IN16
COMA
COMA
VP24FA
Short
Cable
DC Power Supply
IN1
IN2
IN3
IN16
COM1-16
NC
Cabinet
DC Power Supply
AKB331/AKB337
F030110.ai
Figure Connection example of ADV151/ADV161 Voltage Input Mode
Dec. 3, 2021-00