6. OUTLINE
■
STANDARD SPECIFICATIONS
Refer to IM 01E20F02-01E for F
OUNDATION
Fieldbus
communication type and IM 01E20F12-01E for
PROFIBUS PA communication type regarding the items
marked with “
”.
Converter (Integral flowmeter)
The contents of (*1) and (*2) described in the converter
specifications are follows.
*1: Select two points from: one pulse output, one alarm
output, one status input, or two status outputs.
*2: For models without an indicator, the configuration tool
(Such as HHT (handheld terminal) or FieldMate
TM
,
etc.) is necessary to set parameters.
Excitation Method:
• Standard dual frequency excitation:
Size 2.5 to 400 mm (0.1 to 16 in.)
• Enhanced dual frequency excitation:
Size 25 to 200 mm (1.0 to 8.0 in.)
(Optional code HF1 or HF2)
Input Signal (*1) “
”:
One Status Input: Dry contact
Load Resistance: 200
Ω
or less (ON), 100 k
Ω
or more
(OFF)
Output Signals “
”:
• One Current Output: 4 to 20 mA DC (load resistance:
750
Ω
maximum, including cable resistance)
• One Pulse Output (*1):
Transistor contact output (open collector)
Contact capacity: 30 V DC (OFF), 200 mA (ON)
Output rate: 0.0001 to 10,000 pps (pulse/second)
• One Alarm Output (*1):
Transistor contact output (open collector)
Contact capacity: 30 V DC (OFF), 200 mA (ON)
• Two Status Outputs (*1):
Transistor contact output (open collector)
Contact capacity: 30 V DC (OFF), 200 mA (ON)
Communication Signals “
”:
BRAIN or HART communication signal
(Superimposed on the 4 to 20 mA DC signal)
Distance from Power Line: 15 cm (6 in.) or more
(Parallel wiring should be avoided.)
BRAIN:
Communication Distance:
Up to 1.5 km (0.93 miles), when polyethylene insulated
PVC-sheathed cables (CEV cables) are used.
Communication distance varies depending on the type
of cable and wiring used.
Load Resistance:
250 to 450
Ω
(including cable resistance)
Load Capacitance:
0.22
µ
F or less
Load Inductance:
3.3 mH or less
Input Impedance of Communicating Device:
10 k
Ω
or more (at 2.4 kHz)
HART:
Load Resistance:
250 to 600
Ω
(including cable resistance)
Note: HART is a registered trademark of the HART
Communication Foundation.
Data Security During Power Failure:
Data (parameters, totalizer value, etc.) storage by
EEPROM. No back-up battery required.
Indicator (*2):
Full dot-matrix LCD (32
132 pixels)
Lightning Protector:
The lightning protector is built into the current output and
pulse/alarm/status input and output terminals. When
optional code A is selected, the lightning protector is
built into the power terminals.
Protection:
General-purpose Use/Sanitary Type/TIIS Flameproof
type:
IP66, IP67
Explosion proof type except TIIS:
In case of explosion proof type except TIIS, refer to
description of "Enclosure" in "HAZARDOUS AREA
CLASSIFICATION".
Coating:
Case and Cover: Corrosion-resistant coating
Coating Color; Mint green coating (Munsell 5.6 BG
3.3/2.9 or its equivalent)
Converter Material:
Case and Cover : Aluminum alloy
Mounting/Shapes (Integral Flowmeter):
• Electrical Connection:ANSI 1/2 NPT female
ISO M20
1.5 female
JIS G1/2 female
• Direction of Electrical Connection: The direction can be
changed even after delivery.
• Terminal Connection: M4 size screw terminal
Grounding:
Grounding resistance 100
Ω
or less
When optional code A is selected, grounding resistance
10
Ω
or less shall be applied.
* In case of explosion proof type except TIIS, follow
the domestic electrical requirements as regulated
in each country.
* In case of TIIS Flameproof type, refer to descrip-
tion of “HAZARDOUS AREA CLASSIFICATION”.
6.
OUTLINE