3 Installation
3.1 Location
Follow all the local regulations to install the inverter.
Please install the equipment in a location of Dry, Clean, Cool with good ventilation.
Working temperature
:
‐
10
℃‐
40
℃
Storage temperature
:
‐
40
‐
70
℃
Relative Humidity
:
0%
‐
95%
,
non-condensing
Cooling
:
Forced air
3.2 Wiring recommendation
It is suggested the battery bank be kept as close as possible to the inverter. The following able is a suggested
wiring option for 1 meter DC cable.
Please find the following minimum wire size. In case of DC cable longer than 1m, please increase the cross section of
cable to reduce the loss.
Power
DC Input voltage
Wire Gage
Strings
1KW
12V
AWG 8
3
1KW
24V
AWG 8
2
1.5KW
12V
AWG 8
3
1.5KW
24V
AWG 8
2
2KW
12V
AWG 8
5
2KW
24V
AWG 8
3
2KW
48V
AWG 8
2
3KW
12V
AWG 8
7
3KW
24V
AWG 8
4
3KW
48V
AWG 8
2
4KW
24V
AWG 8
5
4KW
48V
AWG 8
2
5KW
24V
AWG 8
6
5KW
48V
AWG 8
3
6KW
24V
AWG 8
7
6KW
48V
AWG 8
4