Any-Power Solution AVR Function
Any-Power Solution Series
LV (NA/JPN)
HV (INTL)
Acceptable Input Voltage Range (Vac)
0-160
0-300
Nominal Input Voltages (Vac)
100
110
120
220
230
240
(A) Line low loss N/W (On battery)
75/65
84/72
92/78
168/14
3
176/15
0
183/156
(B) Line Low comeback N/W (On Boost)
80/70
89/77
97/83
178/15
3
186/16
0
193/166
(C) Line 2nd boost threshold (On Boost)
**
**
**
**
**
**
(D) Line 2nd boost comeback (On normal)
**
**
**
**
**
**
(E) Line 1st boost threshold (On Boost)
90
99
108
198
207
216
(F) Line 1st boost comeback (On normal)
93
103
112
205
215
225
(G) Line buck comeback (On Normal)
106
118
128
235
246
256
(H) Line buck threshold (On Buck)
110
121
132
242
253
264
(I) Line high comeback (On Buck)
115
127
139
253
266
278
(J) Line high loss (On Battery)
120
132
144
263
276
288
2.5.7 Protections
The APC series inverter is equipped with extensive protections against various harsh situations/faults.
These protections include:
AC Input over voltage protection/AC Input low voltage protection
Low battery alarm/High battery alarm
Over temperature protection/Over load protection
Short Circuit protection (1s after fault)
Back feeding protection
When Over temperature /Over load occur, after the fault is cleared, the master switch has to be reset to
restart the inverter.