Yiyuan Electric Co., Ltd www.yiyen.com
9
Charging current for each model
Model
Current
1012E
35+/-5A
1024E
20+/-5A
1512E
45+/-5A
1524E
25+/-5A
2012E
65+/-5A
2024E
30+/-5A
2048E
20+/-5A
3012E
85+/-5A
3024E
45+/-5A
3048E
30+/-5A
4024E
65+/-5A
4048E
35+/-5A
5024E
70+/-5A
5048E
40+/-5A
6024E
85+/-5A
6048E
55+/-5A
2.5.3 Solar Charger*
For APV series, there is a solar charger built in.
Table 1
Electrical Specifications
@ 25
℃
Rated Voltage
12V
24V
Rated Charge Current
40A
Rated Output Current
15A
Self Consumption
At idle < 10mA
Bulk Charge
14.5V(default)
29.0V(default)
Floating Charge
①
13.5V(default)
27.0V(default)
Equalization Charge
①
14.0V(default)
28.0V(default)
Over Charge Disconnection
14.8V
29.6V
Over Charge Recovery
13.6V
27.2V
Over Discharge Disconnection
①
10.8 V(default)
21.6V(default)
Over Discharge Reconnection
12.3V
24.6V
Temperature Compensation
①
-13.2mV/
℃
-26.4mV/
℃
Ambient Temperature
0-40
℃
(full load) 40
-
60
℃
(derating)
Terminal Size
(fine/single wire)
#8AWG
NOTE:
①
The optional battery temperature sensor automatically adjusts the charging process of the controller
according to the type of the battery is selected by user through battery type selector. With the battery
temperature sensor installed, the controller will increase or decrease the battery charging voltage depending