CHEMICAL MAINTENANCE 

 

It  is  not  necessary  to  perform  regular 

chemical  maintenance  on  the  Yazaki 
chiller-heater  itself.    The  chemical 
balance  has  been  established  in  the 
factory during run testing.   Normally,  the 
only chemical that must be maintained is 
the  inhibitor  charge.    By  capturing  non-
condensable gases, as shown in Fig. 12, 
comparison can be made to determine if 
the  normal  hydrogen  byproduct  is  being 
produced  at  anticipated  rates.    If  more 
hydrogen 

is 

being 

produced 

than 

anticipated,  a  maintenance  inhibitor 
charge  may  need  to  be  introduced  into 
the  machine  by  the  ASP.    An  inhibitor 

charge  is  typically  needed  every  three 
years in Yazaki gas-fired chiller-heaters. 
 

 

 

Fig. 12 

– Capturing Gases

 

 

WINTERIZING 

 

When  equipment  is  located  outdoors 

in  climates  subject  to  freezing,  cooling 
water  must  be  drained  from  the  chiller-
heater,  piping,  and  cooling  tower  at  the 
end of the cooling season.  Use of glycol 
may  also  be  permissible.    Consult  the 
Service  Manual  for  details  concerning 
Anti-Freeze Strategies. 

When draining a fluid loop, make sure 

to  blow  through  the  emptied  loop  with 
compressed air 

(or  similar)

.  Blow in both 

directions through the loop so as to blow 
out  as  much  of  the  residual  fluid  as 
possible.    This  is  to  help  prevent 
potential  tube  damage  during  freezing 
conditions. 

 
 

TROUBLESHOOTING 

SYMPTOM:  Chiller-Heater does not operate. 

Possible Cause 

REMEDY 

No High Voltage 

Check the LED for the Power indication on the Control Panel.  If it is not illuminated, check the 
main power disconnect, fuses, and breakers. 

Solution Pump Not Running 

Check for illumination of the "FAILURE" LED in the row of indicator LEDs for the Solution 
Pump.  If lit, check the VFD Controller. 

Manual Reset Device Tripped 

Check the error codes using the display on the front panel or the ACT5 Maintenance Checker 
to identify which device is tripped. 

Unit Overheated 

Check combustion, gas pressure, and vent assembly for conditions that cause over-firing or 
prevent proper venting.  Check the VFD controller for the Solution Pump.  Improper mass flow 
through the machine can cause overheating symptoms. 

 

SYMPTOM:  Poor cooling capacity. 

Possible Cause 

REMEDY 

Poor Vacuum 

Evacuate the machine per normal maintenance procedure. 

High Inlet Cooling Water 
Temperature 

Check the cooling tower fan.  Check the cooling tower fluid level. 

Low Cooling Water Flow Rate 

Check the cooling tower sump and cooling water circuit strainers. 

Condenser/Absorber Fouling, 
Scale Buildup 

Check the cooling water circuit strainers.  It may be necessary to drain the cooling water circuit 
and open the inspection doors on the chiller-heater condenser and absorber for a visual 
confirmation. 

Summary of Contents for AROACE CH-MG150

Page 1: ...ty of this or any other equipment CONTENTS GENERAL Page ABSORPTION PRINCIPLE 2 COOLING OPERATION 3 HEATING OPERATION 4 CONTROLS GENERAL INFORMATION 5 CONTROL ADJUSTMENTS 8 CONTROL SEQUENCE 12 OPERATIO...

Page 2: ...ING INSTRUCTIONS may affect the equipment performance and product Warranty If the equipment does not operate as expected check the Troubleshooting Guide in these instructions BEFORE calling your Yazak...

Page 3: ...bundle The heat absorbed by the cooling water is rejected to a cooling tower or alternative system The liquid refrigerant that drips off the tubing bundle joins the liquid refrigerant that resulted f...

Page 4: ...ed refrigerant vapor and leaving a more concentrated solution The refrigerant vapor flows through a changeover valve into the Evaporator section The concentrated solution flows through another changeo...

Page 5: ...back to the same concentration level as when it started the cycle Absorber ABS Liquid refrigerant that condensed on the outer surface of the Evaporator tubing bundle drips into the Absorber sump Conce...

Page 6: ...ed manner by Building Automation Systems BAS BMS when Remote Operation is engaged Additional controls and interlocks may be required in some instances These controls and their functions can be explain...

Page 7: ...er has been set up at the factory and SHOULD NOT BE ADJUSTED Universal replacements are NOT recommended Only use OEM parts for the solution pump and controller Fig 5 Hitachi VFD Controller Control Pan...

Page 8: ...control box for troubleshooting observe all safety warnings on the chiller heater and in these instructions Only qualified and trained personnel should have access to the live electrical parts inside...

Page 9: ...tioned to the left whenever the unit is to be in normal operating condition Position this switch to the right when adjusting the burner Position this switch to the middle when the unit is to sit dorma...

Page 10: ...ard CAT5 cable one was provided from the factory connect the ACT5 to the Main CPU Board located in the upper right of the control box There is a jack in the upper middle of the CPU Board See Figure 8...

Page 11: ...board could result To engage Economy Mode close a circuit between TB1 75 and TB1 76 When that circuit is closed the Main CPU Board logic will automatically apply a modifier to the temperature set poi...

Page 12: ...tant that the chiller heater have control over the pumps to allow for controlled shut down under normal and abnormal conditions Running the chilled water pump at all times is discouraged as the chille...

Page 13: ...e Absorber and Condenser tubing bundles 4 When two or more absorption chiller heaters are installed in parallel set all units to the same operating mode HEATING 1 Select ON on the DIRECT OPERATION sec...

Page 14: ...epare the unit for long term shutdown Without running in Heat mode some water will be trapped in upper portions of the chiller heater and could potentially damage the unit should it freeze in the wint...

Page 15: ...lves are referred to as Service Valve A upper and Service Valve B lower Refer to Fig 4 for detail on where these valves are located at the front of the unit The evacuation service valves are back seat...

Page 16: ...well on a vessel as large as the chiller heater vacuum section Just because the vacuum pump has stopped producing bubbles in the water bucket does NOT mean the vacuum level is adequate A digital vacu...

Page 17: ...to help prevent potential tube damage during freezing conditions TROUBLESHOOTING SYMPTOM Chiller Heater does not operate Possible Cause REMEDY No High Voltage Check the LED for the Power indication o...

Page 18: ...umn An O mark indicates the potential issue should this line item go out of acceptable range 2 When water temperature rises above 104 F 40 C the tendency for corrosion rises remarkably As such there m...

Page 19: ...e GP sensor reads above 252 F 122 C in heating mode 27 Chilled water flow switch error Flow Switch FS1 is open when it should be closed 28 Cooling water flow switch error Optional cooling water Flow S...

Page 20: ...EMS INC 701 E PLANO PKWY SUITE 305 PLANO TEXAS 75074 6700 Phone 469 229 5443 Fax 469 229 5448 Email yazaki yazakienergy com Web www yazakienergy com This symbol on the product s nameplate means it is...

Reviews: