Terminals with spring clamp technology are used for wiring. The spring clamp technology
allows quick and easy connection of your signal and supply lines.
In contrast to screw terminal connections this type of connection is vibration proof.
U
max
: 240V AC / 30V DC
I
max
: 10A
Cross section: 0.08 ... 1.5mm
2
(AWG 28 ... 16)
Stripping length: 10mm
1.
Insert a suited screwdriver at an angel into the square opening as shown. Press
and hold the screwdriver in the opposite direction to open the contact spring.
2.
Insert the stripped end of wire into the round opening. You can use wires with a
cross section of 0.08mm
2
up to 1.5mm
2
.
3.
By removing the screwdriver, the wire is securely fixed via the spring contact to the
terminal.
(1) DC 24V for power section supply I/O area (max. 10A)
(2) DC 24V for electronic power supply bus coupler and I/O area
Terminals
Requirements for the con-
necting cable
Wiring procedure
Wiring power supply
VIPA System SLIO
Deployment
Wiring
HB300 | SM-S | 02x-1SD10 | en | 20-02