3.5 Demounting and module exchange
A defective module must be replaced immediately.
CAUTION!
–
Demounting respectively module exchange may be performed only
by authorized and qualified personnel.
–
A defective System SLIO safety module may only be replaced by a
System SLIO safety module with the same order number respectively
by a module of the compatibility list, which is under construction.
–
After the module exchange a complete function test inclusive verifica-
tion and validation for the system must be accomplished. This should
accordingly be documented.
–
Proceed with the function test accordingly carefully, since you may
reckon that after the module exchange there is an incorrect behavior
of the machine respectively plant.
–
Defective modules must be labelled as defective and should be sent
back to YASKAWA. A re-use is absolutely prevented by measures
within the quality management with the user.
3.5.1 Proceeding
With demounting and exchange of a module, head module (e.g. bus coupler) or a group
of modules for mounting reasons you have always to remove the electronic module of the
just mounted right module. After the mounting it may be plugged again.
1.
For the exchange of an electronic module, the electronic module may be pulled for-
ward after pressing the unlocking lever at the lower side of the module.
2.
To exchange a System SLIO safety module read the F-address of the address
switch of the module to be changed and take these settings for the replacement
module.
3.
For installation plug the electronic module guided by the strips at the lower side until
this engages audible to the terminal module.
Exchange of an
electronic module
VIPA System SLIO
Deployment
Demounting and module exchange > Proceeding
HB300 | SM-S | 02x-1SD10 | en | 20-02