
Behaviour:
n
Standard module: After PowerON the MF LED of one standard module respectively
more standard modules blinks. The RUN LED remains off.
n
Safety module: After PowerON the MF LED of one safety module respectively more
safety modules is on. The RUN LED remains off.
Cause
: At this position a module is placed, which does not correspond to the configured
module.
Remedy:
Match configuration and hardware structure.
Behaviour:
After PowerON all of the RUN LEDs up to the defective module are flashing.
With all following modules the MF LED is on and the RUN LED is off.
Cause
: The module on the right of the flashing modules is defective.
Remedy:
Replace the defective module.
RUN and MF LED - Error in
configuration
RUN and MF LED - Module
failure
VIPA System SLIO
Product description
SDO 4xDC 24V 0.5A - Operating and display elements
HB300 | SM-S | 02x-1SD10 | en | 20-02
45