Programming 168
PG Option Setup
F1-01
PG Parameter
PG Pulses/Rev
Sets the number of pulses per revolution (PPM) of the encoder
(pulse generator).
0 to
60000
1024
-
Q
-
Q
F1-02
Operation Selection at PG
Open Circuit (PGO)
PG Fdbk Loss Sel
Sets stopping method when a PG open circuit fault (PGO) occurs.
See parameter F1-14.
0: Ramp to stop - Decelerate to stop using the active deceleration
time.
1: Coast to stop
2: Fast - Stop - Decelerate to stop using the deceleration time in
C1-09.
3: Alarm Only - Drive continues operation.
0 to 3
1
-
A
-
A
F1-03
Operation Selection at
Overspeed (OS)
PG Overspeed Sel
Sets the stopping method when an overspeed (OS) fault occurs. See
F1-08 and F1-09.
0: Ramp to stop - Decelerate to stop using the active deceleration
time.
1: Coast to stop
2: Fast - Stop - Decelerate to stop using the deceleration time in
C1-09.
3: Alarm Only - Drive continues operation.
0 to 3
1
-
A
-
A
F1-04
Operation Selection at
Deviation
PG Deviation Sel
Sets the stopping method when a speed deviation (DEV) fault
occurs. See F1-10 and F1-11.
0: Ramp to stop - Decelerate to stop using the active deceleration
time.
1: Coast to stop
2: Fast - Stop - Decelerate to stop using the deceleration time in
C1-09.
3: Alarm Only - Drive continues operation.
0 to 3
3
-
A
-
A
F1-05
PG Rotation Selection
PG Rotation Sel
0: Fwd=C.C.W. - Phase A leads with forward run command.
(Phase B leads with reverse run command.)
1: Fwd=C.W. - Phase B leads with forward run command. (Phase
A leads with reverse run command.)
0 to 1
0
-
A
-
A
F1-06
PG Division Rate (PG Pulse
Monitor)
PG Output Ratio
Sets the division ratio for the pulse monitor of the PG-B2 encoder
feedback option board. This function is not available with the
PG-X2 option board.
Division ratio = (1+ n) /m (n=0 to 1, m=1 to 32)
The first digit of the value of F1-06 stands for n, the second and the
third stand for m. (from left to right).
The possible division ratio settings are:
1/32
≤
F1-06
≤
1
1 to 132
1
-
A
-
A
F1-07
Integral function during
accel/decel selection
PG Ramp PI/I Sel
Sets integral control during acceleration/deceleration to either
enabled or disabled.
0: Disabled - The integral function is not used while accelerating
or decelerating.
1: Enabled - The integral function is used at all times.
0 to 1
0
-
A
-
-
F1-08
Overspeed detection level
PG Overspd Level
Configures the overspeed fault (OS) detection.
OS fault will occur, if the motor speed feedback is greater than the
F1-08 setting for a time longer than F1-09. F1-08 is set as a
percentage of the maximum output frequency (E1-04). See F1-03.
0 to 120
115%
-
A
-
A
F1-09
Overspeed detection delay
time
PG Overspd Time
0.0 to
2.0
0.0 sec
-
A
-
A
F1-10
Excessive speed deviation
detection level
PG Deviate Level
Configures the speed deviation fault (DEV) detection.
DEV fault will occur if the speed deviation is greater than the
F1-10 setting for a time longer than F1-11. F1-10 is set as a
percentage of the maximum output frequency (E1-04).
Speed deviation is the difference between actual motor speed and
the frequency reference command. See F1-04.
0 to 50
10%
-
A
-
A
F1-11
Excessive speed deviation
detection delay time
PG Deviate Time
0.0 to
10.0
0.5 sec
-
A
-
A
Denotes that parameter can be changed when the Drive is running.
Table A.1 F7 Parameter List (Continued)
Parameter
No.
Parameter Name
Digital Operator Display
Description
Setting
Range
Factory
Setting
Control Method
V/F
V/F
w/
PG
Open
Loop
Vector
Flux
Vector