Programming 106
The analog output function selections above correspond to one of the same number U1-xx monitors in the Drive.
Fig. 77 Analog Output Signal Level as a Function of the Monitor Value
Function: Frequency Reference
Setting: 1
The analog output level will correspond to the chosen frequency reference input whether it is input via the digital operator,
analog input, serial communication, option board, or pulse input. 100% will be equivalent to the maximum output frequency
of the Drive (E1-04).
Function: Output Frequency
Setting: 2
The analog output level will correspond to the actual Speed being output by the Drive and will include the acceleration and
deceleration ramps. 100% will be equivalent to the maximum output frequency of the Drive (E1-04).
Function: Output Current
Setting: 3
The analog output level will correspond to the output current level of the Drive. 100% will be equivalent to the Drives rated
output current which is based on the rated capacity of the Drive (o2-04).
Function: Motor Speed
Setting: 5
The analog output level will correspond to the motor speed. 100% will be equivalent to the maximum output frequency of the
Drive (E1-04).
Function: Output Voltage
Setting: 6
36
PID Input
O
O
O
O
37
PID Output
O
O
O
O
38
PID Setpoint
O
O
O
O
44
ASR Output Without Filter
X
X
X
O
45
Feedforward Control Output
X
X
X
O
Table 21 Analog Output Functions
Parameter
Setting
Function
Control Method (A1-02)
V/f
V/f with
PG
Open
Loop
Vector
Flux
Vector
10 V
100%
0
Out
put
V
ol
tage
Monitor
Function Level
20mA
4mA