4.7 Test Run
162
YASKAWA ELECTRIC
TOEP C710606 09B YASKAWA AC Drive V1000 Installation & Start-Up Manual
■
Operation Instructions
The following example illustrates a procedure to run the drive using the digital operator.
Note:
Before starting the motor, set the frequency reference to 6 Hz.
for instructions.
Step
Display/Result
1.
Turn on the power to the drive. The initial display appears.
⇒
2.
Press the
key to select LOCAL. The LO/RE LED will
turn on.
⇒
3.
Press
to give the drive a run command. RUN will light
and the motor will rotate at 6 Hz.
⇒
4.
Ensure the motor is rotating in the correct direction and no faults or
alarms occur.
⇒
5.
If there is no error in step 4, press
to increase the frequency
reference. Increase the frequency in 10 Hz increments verifying
smooth operation results at all speeds. For each frequency monitor
the drive output current (U1-03) through the LED operator to
confirm the current is well below the motor rated current. Example:
6 Hz
→
50 Hz/60 Hz
.
Note:
Refer to Auto-Tuning Errors on page 186
for help with
errors that occur while Auto-Tuning the drive.
STOP
RUN
STOP
Off
On
Motor
Forward