4.7 Test Run
166
YASKAWA ELECTRIC
TOEP C710606 09B YASKAWA AC Drive V1000 Installation & Start-Up Manual
◆
Jog Operation: FJOG/RJOG
Digital inputs programmed as Forward Jog (H1-
= 12) and Reverse Jog (H1-
= 13)
will be Jog inputs that do not require a run command. Closing the terminal set for Forward
Jog input will cause the drive to ramp to the Jog Frequency Reference (d1-17) in the forward
direction. The Reverse Jog will cause the same action in the reverse direction. The Forward
Jog and Reverse Jog can be set independently.
■
Jog Operation Parameters
■
Selections for Digital Input Terminals S1 to S7 (H1-01 to H1-07)
■
Connection Example for the Jog Function
In this example, H1-07 = 12 and d1-17 = 6.0 Hz.
Figure 4.30
Figure 4.30 Jog Command from External Terminals
No.
Name
Description
Setting
Range
Default
Setting
d1-17
Jog Frequency
Reference
Frequency reference when: “Jog Frequency Reference” is
selected via multi-function input terminals. “Jog Frequency
Reference” has priority over “Multi-Step Speed Reference 1 to
16." Parameter d1-17 is also the reference for the JOG key on
the digital operator, and the multi-function inputs “Forward
Jog” and “Reverse Jog.”
0.00 to
400.00
6.00 Hz
Setting
Name
12
FJOG Command (ON: rotates forward at the Jog frequency set to d1-17)
13
RJOG Command (ON: rotates in reverse at the Jog frequency set to d1-17)
R/L1
S/L2
T/L3
U/T1
V/T2
W/T3
M
Three-Phase 200 Vac
(400 Vac)
S7 (FJ0G)
SC
Drive