Drive Models 2
o
0154 to 2
o
0248 and 4
o
0156 to 4
o
0414
WARNING! Crush Hazard. Use an adequate length of wire to ensure a 50° or wider suspension angle as illustrated in
maximum allowable load of the eye bolts cannot be guaranteed when the drive is suspended with the wires at angles less than 50°. Failure
to comply may result in serious injury or death from falling equipment.
1.
Remove the two hanging brackets from the drive lower side panels and bolt them on the top panel.
Note:
Tighten the hanging brackets with the specified tightening torque: M10: 18 to 23 N·m (159 to 204 in-lb),
M12: 32 to 40 N·m (283 to 354 in-lb).
Figure 2.6 Location of Hanging Brackets (Drive Models 2
o
0154 to 2
o
0248 and 4
o
0156 to 4
o
0414)
2.
Pass wire through the holes of all four hanging brackets.
Suspending angle:
50° or greater
Figure 2.7 Drive Suspension Using Wires and Hanging Brackets
(Drive Models 2
o
0154 to 2
o
0248 and 4
o
0156 to 4
o
0414)
3.
Gradually take up the slack in the wires and hoist the drive after the wires are stretched tight.
4.
Lower the drive when ready to install in the enclosure panel. Stop lowering the drive when it is near the floor, then slowly
begin lowering the drive again until the drive is placed correctly.
u
HOA Keypad Remote Usage
n
Remote Operation
The HOA keypad mounted on the drive can be removed and connected to the drive using an extension cable up to 3 m (9.8
ft.) long to facilitate operation when the drive is installed in a location where it can not be easily accessed.
The HOA keypad can also be permanently mounted remote locations such as panel doors using an extension cable and an
installation support set (depending on the installation type).
Note:
Refer to Peripheral Devices & Options on page 251
for information on extension cables and installation support sets.
2.2 Mechanical Installation