n
E2-04: Number of Motor Poles
Set the number of motor poles to E2-04. If Auto-Tuning completes successfully, the value entered to T1-06 will automatically
be saved to E2-04.
No.
Parameter Name
Setting Range
Default
E2-04
Number of Motor Poles
2 to 48
2
n
H1-01 to H1-08: Functions for Terminals S1 to S8
.
No.
Parameter Name
Setting
Range
Default
H1-01
Multi-Function Digital Input Terminal S1 Function Selection
0 to B0
40 (F)
: Forward Run Command (2-Wire sequence)
H1-02
Multi-Function Digital Input Terminal S2 Function Selection
0 to B0
F (F): Through Mode
H1-03
Multi-Function Digital Input Terminal S3 Function Selection
0 to B0
26: External Pump Fault
H1-04
Multi-Function Digital Input Terminal S4 Function Selection
0 to 9F
14: Fault Reset
H1-05
Multi-Function Digital Input Terminal S5 Function Selection
0 to B0
H1-06
Multi-Function Digital Input Terminal S6 Function Selection
0 to B0
H1-07
Multi-Function Digital Input Terminal S7 Function Selection
0 to B0
H1-08
Multi-Function Digital Input Terminal S8 Function Selection
0 to B0
Table 4.12 Multi-Function Digital Input Terminal Settings
Setting
Function
0
3-Wire sequence
2
External Reference 1/2 Selection
3
Multi-Step Speed Reference 1
4
Multi-Step Speed Reference 2
5
Multi-Step Speed Reference 3
6
Jog reference selection
7
Accel/decel time selection 1
8
Baseblock command (N.O.)
9
Baseblock command (N.C.)
A
Accel/decel ramp hold
B
Drive overheat alarm (oH2)
C
Analog terminal input selection
F
Through mode
10
Up command
11
Down command
12
Forward Jog
13
Reverse Jog
14
Fault reset
15
Fast Stop (N.O.)
17
Fast Stop (N.C.)
18
Timer function input
19
PID disable
1A
Accel/decel time selection 2
1B
Program lockout
1E
Reference sample hold
20 to 2F
Ext. pump fault
30
PID integral reset
31
PID integral hold
Setting
Function
32
Multi-Step Speed
Reference 4
34
PID soft starter cancel
35
PID input level selection
40
Forward run command
(2-Wire sequence)
41
Reverse run command
(2-Wire sequence)
42
Run command
(2-Wire sequence 2)
43
FWD/REV command
(2-Wire sequence 2)
47
Node setup
51
Sequence Timer Disable
52
Sequence Timer Cancel
60
DC Injection Braking command
61
External Speed Search
command 1
62
External Speed Search
command 2
63
Field weakening
67
Communications test mode
68
High Slip Braking (HSB)
6A
Drive enable
73
Low City Press
75
Up 2 command
76
Down 2 command
80
HAND Mode
81
HAND Mode 2
82
PI Switch to Aux
4.7 Basic U1000 iQpump Setup and Application Preset Parameters
YASKAWA TOEPYAIUPW01A YASKAWA AC Drive - U1000 iQpump Matrix Drive User Manual
151
4
Start-Up Programming & Operation