
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
S2-05
(320A)
Sequence Timer 1
Reference Source
Tmr 1 Ref Source
0: Operator (d1-01/
Q1-01)
0: Operator (d1-02/
Q1-02)
0: Operator (d1-03/
Q1-03)
0: Operator (d1-04/
Q1-04)
4: Terminals
5: Serial com
6: Option PCB
7: Pulse Input
8: Set by b1-01
Selects the frequency reference source used for running the
drive when sequence timer 1 is active (only applicable when
S2-04 is set to 1 or 2).
0: Operator (d1-01/Q1-01)
1: Operator (d1-02/Q1-02)
2: Operator (d1-03/Q1-03)
3: Operator (d1-04/Q1-04)
4: Terminals
5: Serial communication
6: Option card
7: Pulse input
8: Set by b1-01
Default: 8
Range: 0 to 8
–
S2-06
(320B)
Sequence Timer 2 Start
Time
Tmr 2 Start Time
Sets the start time for timer 2.
Default:
12:00AM
Min.: 12:00AM
Max.: 11:59PM
–
S2-07
(320C)
Sequence Timer 2 Stop
Time
Tmr 2 Stop Time
Sets the stop time for timer 2.
Default:
12:00AM
Min.: 12:00AM
Max.: 11:59PM
–
S2-08
(320D)
Sequence Timer 2 Day
Selection
Tmr 2 Day Sel
0: Timer Disabled
1: Daily
2: Mon - Fri
3: Sat - Sun
4: Monday
5: Tuesday
6: Wednesday
7: Thursday
8: Friday
9: Saturday
10: Sunday
Sets the days for which sequence timer 2 is active.
0: Timer disabled
1: Daily
2: Mon - Fri
3: Sat - Sun
4: Monday
5: Tuesday
6: Wednesday
7: Thursday
8: Friday
9: Saturday
10: Sunday
Default: 0
Range: 0 to 10
–
S2-09
(320E)
Sequence Timer 2
Selection
Tmr 2 Seq Sel
0: Digital Out Only
1: Run
2: Run - PI Disable
3: AllowAlternation
Sets the action that occurs when sequence timer 2 is active.
0: Digital output only
1: Run
2: Run - PI disable
3: Allow Alternation
Default: 0
Range: 0 to 3
S2-10
(320F)
Sequence Timer 2
Reference Source
Tmr 2 Ref Source
0: Operator (d1-01)
1: Operator (d1-02)
2: Operator (d1-03)
3: Operator (d1-04)
4: Terminals
5: Serial Com
6: Option PCB
7: Pulse Input
8: Set by b1-01
Selects the frequency reference source used for running the
drive when sequence timer 2 is active (only applicable when
S2-09 is set to 1 or 2).
0: Operator (d1-01/Q1-01)
1: Operator (d1-02/Q1-02)
2: Operator (d1-03/Q1-03)
3: Operator (d1-04/Q1-04)
4: Terminals
5: Serial communication
6: Option card
7: Pulse input
8: Set by b1-01
Default: 8
Range: 0 to 8
–
S2-11
(3210)
Sequence Timer 3 Start
Time
Tmr 3 Start Time
Sets the start time for timer 3.
Default:
12:00AM
Min.: 12:00AM
Max.: 11:59PM
–
S2-12
(3211)
Sequence Timer 3 Stop
Time
Tmr 3 Stop Time
Sets the stop time for timer 3.
Default:
12:00AM
Min.: 12:00AM
Max.: 11:59PM
–
B.14 S: Special Application
YASKAWA TOEPYAIUPW01A YASKAWA AC Drive - U1000 iQpump Matrix Drive User Manual
349
B
Parameter List